November 03, 2026
Generated lab notebook from daily_summary, plan_journal, plan_delivery_log, and setpoint audit data. It is intentionally chronological and may include in-progress cycles before validation.
Planner Execution Ledger
Planner checkpoints can acknowledge that the active plan is still suitable without writing a new public plan ID. Those no-change decisions are part of the audit trail.
6
3
2
0
| Event | Delivered | Type | Status | Note |
|---|---|---|---|---|
| End-of-day review and reset | 00:17 | MIDNIGHT | plan_written | Wrote public plan iris-20261103-0017. Resolved 00:20 MDT. |
| Morning planning cycle | 06:34 | SUNRISE | plan_written | Wrote public plan iris-20261103-0636. Resolved 06:41 MDT. |
| Solar peak planning checkpoint | 11:45 | SOLAR_MAX | action_completed | Delivery recorded without a public plan write. Resolved 11:47 MDT. |
| Peak Stress | 13:45 | TRANSITION | acked | Acknowledged: Peak-stress conditions remain within the active plan's expected window: indoor VPD 1.19 kPa is only 0.03 above the 1.16 edge with 14°F dew margin, temperature is 76.6°F with no heat stress, and forecast VPD eases after 15:00. Today's 3.48 nominal VPD-high hours remain within the plan's <=4h expectation; no additional tunable change is warranted. Resolved 13:46 MDT. |
| Decline | 15:56 | TRANSITION | acked | Acknowledged: No tunable change: indoor VPD is only marginally above the current high edge (1.05 vs 0.99 kPa), with healthy 11.4°F dew margin and no wet relays active. The governing plan already tapers at 16:00 (engage/all 1.0/1.2 kPa, gap 49 s, fog escalation 0.3) and again at 18:00 (gap 60 s, fog 0.4); cool evening forecast supports that posture. Keep the brief recovery shoulder rather than adding an immediate override; re-evaluate on observed VPD recovery, not forecast decline alone. Resolved 15:57 MDT. |
| Evening planning cycle | 16:57 | SUNSET | plan_written | Wrote public plan iris-20261103-1657. Resolved 16:59 MDT. |
🌅 Morning Cycle (12:20 AM) — iris-20261103-0017
validated
5/10
band_track_fraction, cold_vent_guard_delta_f, cool_exit_hysteresis_f, cool_stage2_exit_hysteresis_f, cool_stage2_over_high_f, direct_wet_stress_min_dew_margin_f, direct_wet_stress_vpd_margin_kpa, dwell_gate_ms ...
Reflection
Validating previous cycle: iris-20261102-1658
Previous hypothesis: {“conditions”:{“outdoor_temp_peak_f”:50.0,“outdoor_rh_min_pct”:42.0,“solar_peak_w_m2”:0.0,“cloud_cover_avg_pct”:87.25,“notes”:“Tonight: indoor 72.0F/VPD 0.96, dew margin 12.8F; forecast low 39F by Tue 07:00. Partial score 73.9 vs 7d 70.7; temp compliance 36.9% trails VPD 66.5%, with 10.07h cold and 5.35h VPD-high nominal stress. Cost unavailable.”},“stress_windows”:[{“kind”:“cold”,“start”:“2026-11-02T17:00:00-07:00”,“end”:“2026-11-03T07:00:00-07:00”,“severity”:“high”,“mitigation”:“Retain heat with stable dwell; avoid cold exchange; low-duty wet assist only on live VPD excess, dew floor 8F.”}],“rationale”:[{“parameter”:“mister_engage_kpa”,“old_value”:1.264,“new_value”:1.04,“forecast_anchor”:“VPD 0.96 vs high edge 0.99; dew margin 12.8F; outdoor falls to 39F.”,“expected_effect”:“Keep assist available near live edge while low duty limits added VPD-low and dew risk… Result: Window-only evidence for iris-20261103-0017 (00:20–06:41 MST): observed nominal cold stress 4.44h, VPD-high 1.66h, VPD-low 0.44h, and dew-risk 0h; the scored window fractions were 27.2% temp and 65.6% VPD (joint 5.6%). This partially matched the intended frost posture: no dew-risk and VPD-high was lower than the cited prior full-day 6.65h, but VPD-low was not zero and cold exposure remained material. Attribution is weak: daily scored coverage/targets are unverified, resource data unavailable, and no physical crop outcome evidence; do not infer causal benefit. Score: 5/10
Hypothesis
Testing: Guarded frost-night to live-confirmed dry morning; maintain band-relative assist, no causal claim. Expected outcome: No VPD-low or dew-risk overshoot; reduce VPD-high from the prior 6.65h/day where live demand and dew margin permit; keep wet assist available at the edge.
Setpoints
Tuesday November 03
Primary crop-band changes:
| Time | Values | Note |
|---|---|---|
| 00:17 | hyst 0.1875 | Hold heat and avoid cold exchange; no wet demand below live |
| 04:45 | hyst 0.1875 | Frost-adjacent pre-dawn; preserve heat, avoid cold exchange, |
| 07:00 | hyst 0.1875 | At sunrise, keep moisture band-coupled as live VPD leaves th |
| 11:00 | hyst 0.1875 | Dry ramp approaches outdoor VPD 1.14; retain bounded wet ass |
Tactical tunable changes:
| Time | Values | Note |
|---|---|---|
| 00:17 | s2 1.875; cool_exit 1.6; all_fans 0; dw_stress 1; engage 0.794; all 1; pulse 33.75; gap 33.75; wt 1.7 | Hold heat and avoid cold exchange; no wet demand below live |
| 04:45 | s2 1.875; cool_exit 1.6; all_fans 0; dw_stress 1; engage 0.794; all 1; pulse 33.75; gap 33.75; wt 1.7 | Frost-adjacent pre-dawn; preserve heat, avoid cold exchange, |
| 07:00 | s2 1.8025000000000002; cool_exit 1.6; all_fans 0; dw_stress 1; engage 0.794; all 1; pulse 33.75; gap 37.5; wt 1.7 | At sunrise, keep moisture band-coupled as live VPD leaves th |
| 11:00 | s2 1.7875; cool_exit 1.6; all_fans 0; dw_stress 1; engage 0.794; all 1; pulse 37.5; gap 33.75; wt 1.7000000000000002 | Dry ramp approaches outdoor VPD 1.14; retain bounded wet ass |
Changed secondary parameters:
| Time | Parameter | Change |
|---|---|---|
| 00:17 | band_track_fraction | initial 0 |
| 00:17 | cold_vent_guard_delta_f | initial 14 |
| 00:17 | cool_stage2_exit_hysteresis_f | initial 1 |
| 00:17 | direct_wet_stress_min_dew_margin_f | initial 8 |
| 00:17 | direct_wet_stress_vpd_margin_kpa | initial 0.05 |
| 00:17 | dwell_gate_ms | initial 210000 |
| 00:17 | enthalpy_close | initial 1 |
| 00:17 | enthalpy_open | initial -2 |
| 00:17 | fog_escalation_kpa | initial 0.25 |
| 00:17 | heat_hysteresis | initial 1 |
| 00:17 | min_fog_off_s | initial 60 |
| 00:17 | min_fog_on_s | initial 63.75 |
| 00:17 | mist_backoff_s | initial 600 |
| 00:17 | mist_max_closed_vent_s | initial 600 |
| 00:17 | mist_thermal_relief_s | initial 90 |
| 00:17 | mister_all_delay_s | initial 75 |
| 00:17 | mister_engage_delay_s | initial 37.5 |
| 00:17 | mister_water_budget_gal | initial 120 |
| 00:17 | night_vpd_bias_kpa | initial 0 |
| 00:17 | outdoor_staleness_max_s | initial 600 |
| 00:17 | sw_dwell_gate_enabled | initial 1 |
| 00:17 | sw_fog_closes_vent | initial 1 |
| 00:17 | sw_mister_closes_vent | initial 0 |
| 00:17 | sw_summer_vent_enabled | initial 1 |
| 00:17 | temp_hysteresis | initial 1.6 |
| 00:17 | vent_exchange_fraction | initial 0.3 |
| 00:17 | vent_prefer_dp_delta_f | initial 6 |
| 00:17 | vent_prefer_temp_delta_f | initial 10 |
| 00:17 | vpd_watch_dwell_s | initial 52.5 |
| 07:00 | cold_vent_guard_delta_f | 14 → 12 |
| 07:00 | min_fog_off_s | 60 → 66 |
| 07:00 | min_fog_on_s | 63.75 → 61.5 |
| 07:00 | vent_prefer_temp_delta_f | 10 → 8 |
| 11:00 | min_fog_off_s | 66 → 60 |
| 11:00 | min_fog_on_s | 61.5 → 63.75 |
| 11:00 | vent_prefer_dp_delta_f | 6 → 5 |
🌅 Morning Cycle (6:41 AM) — iris-20261103-0636
validated
4/10
band_track_fraction, cold_vent_guard_delta_f, cool_exit_hysteresis_f, cool_stage2_exit_hysteresis_f, cool_stage2_over_high_f, direct_wet_stress_min_dew_margin_f, direct_wet_stress_vpd_margin_kpa, dwell_gate_ms ...
Reflection
Validating previous cycle: iris-20261102-1658
Result: Plan window scorecard (06:41–16:55 MST): score 74.3; contract-2 binary temp/VPD fractions 36.4%/63.6%; nominal cold stress 4.37h and VPD-high 2.51h, with 0 heat/VPD-low/dew-risk hours. Cold remained the larger axis stress, broadly consistent with the forecasted frost-adjacent load but partly outside the plan’s stated overnight window; daytime VPD-high was moderate, not eliminated. Outdoor peak/RH-min/solar were 55.5°F/56%/446 W/m² versus predicted 59°F/31%/474, so the dry-ramp forecast overstated dryness. Plan writes mostly matched/already-at-value, but one pulse-gap mismatch and one miss occurred; persistent guardrail clamps limit confidence that requested moisture thresholds were consumed. Costs/resource terms unavailable; no causal crop or resource benefit established. Score: 4/10
Hypothesis
Testing: Test a frost-dawn, live-edge-only moisture ramp on a cool day; no causal crop or resource claim. Expected outcome: VPD-high nominal stress ⇐4h; VPD-low and dew-risk hours 0; preserve heat through the forecast 34F dawn; misting within the 120-gal budget. Costs remain unavailable.
Conditions
59.0°F
31.0%
474.0 W/m²
15.0%
High 59F, RH min31%, outdoor VPD1.17; indoor0.71 below high0.902, dew margin11.7F. Next dawn near34F. Yesterday: score77.8, temp/VPD28.2/71.1%, cold/VPD-high16.53/6.65h; costs unavailable, water8gal vs 7d165. Earlier self-grades exceeded anchors (1658 7.3/4; 1240 4/1; 1240 logged 140 VPD guardrail events,106 held); no causal benefit established.
Expected stress windows
Only respond to measured excess: engage near high+0.05, all-zone near high+0.25, fog near +0.25 with dew margin >=8F.
Retain heat and avoid unnecessary cold exchange; wet only on measured VPD-high with dew margin >=8F.
Parameter rationale
Keep first-stage wet assist reachable only near a measured high-band excess; avoid humid-dawn wetting.
Escalate to all-zone rotation only on sustained additional VPD excess, limiting unnecessary wetting.
Setpoints
Tuesday November 03
Primary crop-band changes:
| Time | Values | Note |
|---|---|---|
| 06:36 | hyst 0.1975 | Cold dawn: retain heat; indoor VPD remains below the high ed |
| 09:00 | hyst 0.1975 | Morning ramp: preserve cold-air restraint; allow moisture re |
| 13:00 | hyst 0.1975 | Peak forecast VPD is 1.17 outdoors; permit bounded wet assis |
| 16:00 | hyst 0.1975 | Declining solar: keep edge-coupled assist available until ob |
| 18:00 | hyst 0.1975 | Evening cold front: restrict exchange, preserve heat; taper |
Tactical tunable changes:
| Time | Values | Note |
|---|---|---|
| 06:36 | s2 1.915; cool_exit 1.78; all_fans 0; dw_stress 0; engage 0.9580000000000001; all 1.158; pulse 30; gap 60; wt 1.3133333333333332 | Cold dawn: retain heat; indoor VPD remains below the high ed |
| 09:00 | s2 1.8699999999999999; cool_exit 1.78; all_fans 0; dw_stress 0; engage 0.9580000000000001; all 1.158; pulse 30; gap 52.5; wt 1.4533333333333334 | Morning ramp: preserve cold-air restraint; allow moisture re |
| 13:00 | s2 1.825; cool_exit 1.78; all_fans 0; dw_stress 0; engage 0.9580000000000001; all 1.158; pulse 33.75; gap 41.25; wt 1.6 | Peak forecast VPD is 1.17 outdoors; permit bounded wet assis |
| 16:00 | s2 1.855; cool_exit 1.78; all_fans 0; dw_stress 0; engage 0.9580000000000001; all 1.158; pulse 30; gap 48.75; wt 1.5 | Declining solar: keep edge-coupled assist available until ob |
| 18:00 | s2 1.915; cool_exit 1.78; all_fans 0; dw_stress 0; engage 0.9580000000000001; all 1.158; pulse 30; gap 60; wt 1.3 | Evening cold front: restrict exchange, preserve heat; taper |
Changed secondary parameters:
| Time | Parameter | Change |
|---|---|---|
| 06:36 | band_track_fraction | initial 0 |
| 06:36 | cold_vent_guard_delta_f | initial 14 |
| 06:36 | cool_stage2_exit_hysteresis_f | initial 1 |
| 06:36 | direct_wet_stress_min_dew_margin_f | initial 8 |
| 06:36 | direct_wet_stress_vpd_margin_kpa | initial 0.05 |
| 06:36 | dwell_gate_ms | initial 240000 |
| 06:36 | enthalpy_close | initial 1 |
| 06:36 | enthalpy_open | initial -2 |
| 06:36 | fog_escalation_kpa | initial 0.35 |
| 06:36 | heat_hysteresis | initial 1 |
| 06:36 | min_fog_off_s | initial 108 |
| 06:36 | min_fog_on_s | initial 45.75 |
| 06:36 | mist_backoff_s | initial 600 |
| 06:36 | mist_max_closed_vent_s | initial 600 |
| 06:36 | mist_thermal_relief_s | initial 90 |
| 06:36 | mister_all_delay_s | initial 84 |
| 06:36 | mister_engage_delay_s | initial 42 |
| 06:36 | mister_water_budget_gal | initial 120 |
| 06:36 | night_vpd_bias_kpa | initial 0 |
| 06:36 | outdoor_staleness_max_s | initial 600 |
| 06:36 | sw_dwell_gate_enabled | initial 1 |
| 06:36 | sw_fog_closes_vent | initial 1 |
| 06:36 | sw_mister_closes_vent | initial 0 |
| 06:36 | sw_summer_vent_enabled | initial 1 |
| 06:36 | temp_hysteresis | initial 1.78 |
| 06:36 | vent_exchange_fraction | initial 0.3 |
| 06:36 | vent_prefer_dp_delta_f | initial 6 |
| 06:36 | vent_prefer_temp_delta_f | initial 10 |
| 06:36 | vpd_watch_dwell_s | initial 60 |
| 09:00 | fog_escalation_kpa | 0.35 → 0.3 |
| 09:00 | min_fog_off_s | 108 → 90 |
| 09:00 | min_fog_on_s | 45.75 → 52.5 |
| 13:00 | fog_escalation_kpa | 0.3 → 0.25 |
| 13:00 | min_fog_off_s | 90 → 72 |
| 13:00 | min_fog_on_s | 52.5 → 59.25 |
| 16:00 | fog_escalation_kpa | 0.25 → 0.3 |
| 16:00 | min_fog_off_s | 72 → 84 |
| 16:00 | min_fog_on_s | 59.25 → 54.75 |
| 18:00 | fog_escalation_kpa | 0.3 → 0.35 |
| 18:00 | min_fog_off_s | 84 → 108 |
| 18:00 | min_fog_on_s | 54.75 → 45.75 |
🌆 Evening Cycle (4:59 PM) — iris-20261103-1657
validated
4/10
band_track_fraction, cold_vent_guard_delta_f, cool_exit_hysteresis_f, cool_stage2_exit_hysteresis_f, cool_stage2_over_high_f, direct_wet_stress_min_dew_margin_f, direct_wet_stress_vpd_margin_kpa, dwell_gate_ms ...
Reflection
Validating previous cycle: iris-20261103-0636
Previous hypothesis: {“conditions”:{“outdoor_temp_peak_f”:59,“outdoor_rh_min_pct”:31,“solar_peak_w_m2”:474,“cloud_cover_avg_pct”:15,“notes”:“High 59F, RH min31%, outdoor VPD1.17; indoor0.71 below high0.902, dew margin11.7F. Next dawn near34F. Yesterday: score77.8, temp/VPD28.2/71.1%, cold/VPD-high16.53/6.65h; costs unavailable, water8gal vs 7d165. Earlier self-grades exceeded anchors (1658 7.3/4; 1240 4/1; 1240 logged 140 VPD guardrail events,106 held); no causal benefit established.”},“stress_windows”:[{“kind”:“vpd_high”,“start”:“2026-11-03T12:00:00-07:00”,“end”:“2026-11-03T16:00:00-07:00”,“severity”:“medium”,“mitigation”:“Only respond to measured excess: engage near high+0.05, all-zone near high+0.25, fog near +0.25 with dew margin >=8F… Result: Window evidence for iris-20261103-1657 only (about 0.306 day fraction): planner_score 64.1; contract-2 binary temp/VPD compliance 0.0%/99.4%; nominal stress cold 1.83h, VPD-high 0h, VPD-low 0.01h, dew-risk 0h. The overnight/cold posture coincided with minimal wet overshoot and no dew-risk, but temperature compliance remained poor and causal attribution is weak because coverage/targets are unverified. kWh, therms, and cost are unavailable; total-water history shows 10 gal for Nov 3 but includes greenhouse, sink, and hose. No durable lesson justified. Score: 4/10
Hypothesis
Testing: Conservative frost-adjacent overnight posture; assess relay stability and moisture guardrail holds, without claiming causal crop or resource benefit. Expected outcome: Overnight: cold stress ⇐5h, VPD-high ⇐3h, and VPD-low/dew-risk 0h; retain heat through the 38F dawn. Costs remain unavailable, so no savings claim.
Conditions
55.0°F
41.0%
0.0 W/m²
56.0%
Mostly cloudy, variable sky; forecast falls to 38F before dawn. Indoor 72.3F/VPD 0.87, dew margin 11.2F; house VPD is just below the current 0.95 high edge. Prior plan scored 4 vs deterministic anchor 1; 112/124 VPD guardrail events held changes, so efficacy is uncertain.
Expected stress windows
Preserve heat with stable dwell and conservative air exchange; wet only on live high-edge demand with dew margin >=8F.
Parameter rationale
Dampen heater/vent reversals through cold dawn without changing crop bands.
Limit unnecessary overnight wet cycling while retaining live-edge response if indoor VPD rises.
Setpoints
Tuesday November 03
Primary crop-band changes:
| Time | Values | Note |
|---|---|---|
| 16:57 | hyst 0.2175 | evening_settle: maintain heat as outdoor air cools; avoid we |
Tactical tunable changes:
| Time | Values | Note |
|---|---|---|
| 16:57 | s2 1.935; cool_exit 2.14; all_fans 0; dw_stress 0; engage 0.997; all 1.197; pulse 30; gap 48.75; wt 1.4666666666666668 | evening_settle: maintain heat as outdoor air cools; avoid we |
Wednesday November 04
Primary crop-band changes:
| Time | Values | Note |
|---|---|---|
| 00:00 | hyst 0.22249999999999998 | midnight_posture: outdoor VPD is declining; keep exchange co |
| 05:00 | hyst 0.22249999999999998 | pre_dawn: protect heat through the 38F low; preserve only de |
Tactical tunable changes:
| Time | Values | Note |
|---|---|---|
| 00:00 | s2 1.95; cool_exit 2.23; all_fans 0; dw_stress 0; engage 0.997; all 1.197; pulse 30; gap 52.5; wt 1.4 | midnight_posture: outdoor VPD is declining; keep exchange co |
| 05:00 | s2 1.95; cool_exit 2.23; all_fans 0; dw_stress 0; engage 0.997; all 1.197; pulse 30; gap 52.5; wt 1.4133333333333333 | pre_dawn: protect heat through the 38F low; preserve only de |
Changed secondary parameters:
| Time | Parameter | Change |
|---|---|---|
| 16:57 | band_track_fraction | initial 0 |
| 16:57 | cold_vent_guard_delta_f | initial 12 |
| 16:57 | cool_stage2_exit_hysteresis_f | initial 1 |
| 16:57 | direct_wet_stress_min_dew_margin_f | initial 8 |
| 16:57 | direct_wet_stress_vpd_margin_kpa | initial 0.05 |
| 16:57 | dwell_gate_ms | initial 300000 |
| 16:57 | enthalpy_close | initial 1 |
| 16:57 | enthalpy_open | initial -2 |
| 16:57 | fog_escalation_kpa | initial 0.4 |
| 16:57 | heat_hysteresis | initial 1 |
| 16:57 | min_fog_off_s | initial 84 |
| 16:57 | min_fog_on_s | initial 54.75 |
| 16:57 | mist_backoff_s | initial 600 |
| 16:57 | mist_max_closed_vent_s | initial 600 |
| 16:57 | mist_thermal_relief_s | initial 90 |
| 16:57 | mister_all_delay_s | initial 102 |
| 16:57 | mister_engage_delay_s | initial 51 |
| 16:57 | mister_water_budget_gal | initial 120 |
| 16:57 | night_vpd_bias_kpa | initial 0 |
| 16:57 | outdoor_staleness_max_s | initial 600 |
| 16:57 | sw_dwell_gate_enabled | initial 1 |
| 16:57 | sw_fog_closes_vent | initial 1 |
| 16:57 | sw_mister_closes_vent | initial 0 |
| 16:57 | sw_summer_vent_enabled | initial 1 |
| 16:57 | temp_hysteresis | initial 2.14 |
| 16:57 | vent_exchange_fraction | initial 0.3 |
| 16:57 | vent_prefer_dp_delta_f | initial 8 |
| 16:57 | vent_prefer_temp_delta_f | initial 8 |
| 16:57 | vpd_watch_dwell_s | initial 75 |
| 00:00 | cold_vent_guard_delta_f | 12 → 14 |
| 00:00 | dwell_gate_ms | 300000 → 315000 |
| 00:00 | min_fog_off_s | 84 → 90 |
| 00:00 | min_fog_on_s | 54.75 → 52.5 |
| 00:00 | mister_all_delay_s | 102 → 106.5 |
| 00:00 | mister_engage_delay_s | 51 → 53.25 |
| 00:00 | temp_hysteresis | 2.14 → 2.23 |
| 00:00 | vent_prefer_dp_delta_f | 8 → 10 |
| 00:00 | vent_prefer_temp_delta_f | 8 → 10 |
| 00:00 | vpd_watch_dwell_s | 75 → 78.75 |
End-of-Day Summary
Climate
60.1–82.5°F; avg 68.4°F
0.39–1.38 kPa; avg 0.83 kPa
51.8–80.3%
Interior Light Evidence
- Crop DLI: unavailable
- Reason:
source_reading_missing - Provenance:
legacy_invalid_exterior_proxy_plus_fixture_estimate - Validity:
dli-validity-v1; 2024-01-01T00:00:00+00:00 → open - Qualified-light minutes and photoperiod remain independent of unavailable DLI.
Stress Hours
- Heat stress (>85°F): 0.0h
- VPD stress (>2.0 kPa): 6.3h
- Cold stress (<55°F): 16.8h
Economics
Not available
USD 1.33
Not available
Not available
Equipment Runtimes
| Equipment | Runtime | Reading |
|---|---|---|
| Fan 1 | 0 min | Primary exhaust runtime. |
| Fan 2 | 4 min | Secondary exhaust runtime. |
| Vent | 4 min | Intake vent runtime. |
| Fog | 6 min | Fogger runtime. |
| Heat 1 electric | 1260 min | Electric heater runtime. |
| Heat 2 gas | 128 min | Gas heater runtime. |
| Grow lights | 1121 min | Supplemental lighting runtime. |
| Mister south | 0.00h | South mister runtime. |
| Mister west | 0.00h | West mister runtime. |
| Mister center | 0.00h | Center mister runtime. |
Crop Health (Gemini Vision)
| Crop | Zone | Health | Observations | Note |
|---|---|---|---|---|
| Lime Tree | west | 64% | 8 | Observation notes are collapsed below to avoid publishing partial vision snippets. |
| Vanda Orchids | center | 70% | 4 | Observation notes are collapsed below to avoid publishing partial vision snippets. |
| pepper | east | 70% | 3 | Observation notes are collapsed below to avoid publishing partial vision snippets. |
Vision observation notes
Hanging plants (likely orchids or similar epiphytes) are visible in the center and right. Leaves appear turgid and healthy. Roots are exposed and white, indicating good hydration. || Large potted citrus tree visible on the right side. Foliage appears green and turgid. No soil moisture data available, but visual health is good. || Large potted tree visible on the right side (west). Foliage appears dense and healthy. Soil moisture data is missing, but visual inspection shows no signs of wilting or yellowing. || [potential water stress] Vegetative growth observed on the left-side shelving. Soil moisture reading for the West zone is missing, making precise hydration status difficult to confirm, though plants appear structurally sound. || [unknown soil moisture] Potted citrus tree visible on the right side (west zone). Leaves appear green but sensor data for soil moisture is missing, making hydration status uncertain. || [unknown soil moisture] Potted plant visible on the right (west) side.
Hanging baskets visible in the center; roots appear healthy and spread out. No obvious wilting or leaf drop observed in the infrared spectrum. || Hanging orchids visible in the center background. Roots appear white and healthy, indicating good hydration and aeration. Leaves are green and upright. || [exposed roots, potential dehydration] Hanging baskets visible in the center background. Roots appear exposed and dry, which is typical for Vanda but requires monitoring given the 0 lux light reading (likely night cycle). || [root exposure, potential desiccation risk] Hanging baskets visible in the upper center. Roots appear exposed and dry. The 0 lux reading suggests it is nighttime, but the lack of visible misting activity combined with 68% RH may be borderline for epiphytic roots.
Seedlings visible on the right-side shelving units appear upright and uniform. No visible wilting or discoloration. || Seedlings visible on the shelving unit on the left side of the frame. Plants appear upright and healthy, though low light conditions (0 lux) may limit growth. || [potential heat stress] Seedlings located in blue trays on the right-side shelving. While green, the ambient temperature of 81.7°F is high for this stage.
Hourly Pattern
| Hour | Temperature | VPD | RH |
|---|---|---|---|
| 10:00 | 73.2°F | 1.07 kPa | 61.7% |
| 11:00 | 74.6°F | 1.14 kPa | 61.2% |
| 12:00 | 76.4°F | 1.09 kPa | 64.9% |
| 13:00 | 76.6°F | 1.10 kPa | 64.7% |
| 14:00 | 76.9°F | 1.09 kPa | 65.5% |
| 15:00 | 75.7°F | 1.05 kPa | 65.3% |
| 16:00 | 74.0°F | 1.04 kPa | 63.9% |
| 17:00 | 72.6°F | 1.07 kPa | 61.0% |
| 18:00 | 71.2°F | 1.02 kPa | 61.0% |
| 19:00 | 68.1°F | 0.87 kPa | 62.8% |
| 20:00 | 66.3°F | 0.84 kPa | 62.0% |
| 21:00 | 65.0°F | 0.84 kPa | 60.2% |
| 22:00 | 63.3°F | 0.82 kPa | 59.0% |
| 23:00 | 62.0°F | 0.75 kPa | 60.4% |
| 00:00 | 61.8°F | 0.76 kPa | 60.0% |
| 01:00 | 61.0°F | 0.72 kPa | 61.0% |
| 02:00 | 60.7°F | 0.66 kPa | 63.5% |
| 03:00 | 60.3°F | 0.60 kPa | 66.7% |
| 04:00 | 60.7°F | 0.57 kPa | 68.6% |
| 05:00 | 62.6°F | 0.63 kPa | 67.5% |
| 06:00 | 64.1°F | 0.68 kPa | 66.6% |
| 07:00 | 66.0°F | 0.78 kPa | 64.4% |
| 08:00 | 68.4°F | 0.90 kPa | 62.1% |
| 09:00 | 71.4°F | 1.07 kPa | 59.3% |
7-Day Stress Context
| Date | Heat | VPD high | Cold |
|---|---|---|---|
| 2026-10-28 | 0.0h | 4.8h | 16.7h |
| 2026-10-29 | 0.0h | 6.5h | 17.0h |
| 2026-10-30 | 0.0h | 4.2h | 16.7h |
| 2026-10-31 | 0.0h | 4.3h | 17.0h |
| 2026-11-01 | 0.0h | 4.8h | 17.8h |
| 2026-11-02 | 0.0h | 6.7h | 16.5h |
| 2026-11-03 | 0.0h | 6.3h | 16.8h |