November 09, 2026
Generated lab notebook from daily_summary, plan_journal, plan_delivery_log, and setpoint audit data. It is intentionally chronological and may include in-progress cycles before validation.
Planner Execution Ledger
Planner checkpoints can acknowledge that the active plan is still suitable without writing a new public plan ID. Those no-change decisions are part of the audit trail.
9
6
1
0
| Event | Delivered | Type | Status | Note |
|---|---|---|---|---|
| End-of-day review and reset | 00:15 | MIDNIGHT | plan_written | Wrote public plan iris-20261109-0015. Resolved 00:18 MDT. |
| Morning planning cycle | 06:39 | SUNRISE | plan_written | Wrote public plan iris-20261109-0640. Resolved 06:42 MDT. |
| Forecast deviation | 08:50 | FORECAST_DEVIATION | plan_written | Wrote public plan iris-20261109-0850. Resolved 08:52 MDT. |
| Forecast deviation | 10:34 | FORECAST_DEVIATION | plan_written | Wrote public plan iris-20261109-1034. Resolved 10:38 MDT. |
| Solar peak planning checkpoint | 11:45 | SOLAR_MAX | action_completed | Delivery recorded without a public plan write. Resolved 11:46 MDT. |
| Peak Stress | 13:44 | TRANSITION | action_completed | Delivery recorded without a public plan write. Resolved 13:46 MDT. |
| Decline | 15:49 | TRANSITION | acked | Acknowledged: Decline review: indoor VPD 0.96 kPa is only slightly above the 0.90 high edge (east 1.17), dew margin 9.1°F, and all wet relays are off; the open VPD-stress alert remains relevant, so no premature extra taper. The active plan already has a 17:00 decline waypoint raising engage to 1.0, widening pulse gap to 38s, and fog escalation to 0.20 before the forecast 35°F frost night; no additional tunable change needed. Resolved 15:50 MDT. |
| Evening planning cycle | 16:49 | SUNSET | plan_written | Wrote public plan iris-20261109-1652. Resolved 16:53 MDT. |
| Forecast deviation | 16:49 | FORECAST_DEVIATION | plan_written | Wrote public plan iris-20261109-1649. Resolved 16:52 MDT. |
🌅 Morning Cycle (12:18 AM) — iris-20261109-0015
validated
4/10
band_track_fraction, cold_vent_guard_delta_f, cool_exit_hysteresis_f, cool_stage2_exit_hysteresis_f, cool_stage2_over_high_f, direct_wet_stress_min_dew_margin_f, direct_wet_stress_vpd_margin_kpa, dwell_gate_ms ...
Reflection
Validating previous cycle: iris-20261108-1655
Previous hypothesis: {“conditions”:{“outdoor_temp_peak_f”:71.0,“outdoor_rh_min_pct”:11.0,“solar_peak_w_m2”:509.0,“cloud_cover_avg_pct”:1.0,“notes”:“Clear night to 38F; tomorrow forecast 71F, 11% RH, 2.31 kPa VPD, 509 W/m2 solar. Current house 74.1F/0.74 kPa, dew margin 8.6F; today’s minimum 3.7F. Score 73; binary temp/VPD 96/53.3%; VPD-low 7.58h, dew risk 0.1h; costs unavailable. Plan iris-20261108-0015 self-grade 5 vs anchor 2: 6.4h window, 2.03h VPD-low, 42 VPD-high guardrail events (27 held), so attribution weak; morning handoff untested. Dryout: 6 ineffective, 2 insufficient; safety pass; 3 daytime actions.”},“stress_windows”:[{“kind”:“cold”,“start”:“2026-11-08T20:00:00-07:00”,“end”:“2026-11-09T07:00:00-07:00”,“severity”:“medium”,“mitigation”:“Retain heat, avoid unnecessary cold exchange and hold an 8F dew margin; no forecast-only wetting… Result: Completed unevaluated plan iris-20261109-0015 governed only a 0.074-day (~1.8 h) window before replacement. Its scoped scorecard shows planner_score 70.3, contract-2 binary both/temp/VPD 45.6%/96.2%/48.1%, 0.67 nominal stress h (0.02 cold, 0.65 VPD-low, 0 heat/VPD-high), so cold/temperature control was contained but the low-VPD recovery hypothesis was not demonstrated. Nov 8 full-day context: score 76.2 vs 7d 76.5; binary temp 97.2%, VPD 47.6%; stress 12.42 h VPD-low, 0.67 cold, 0.17 VPD-high; minimum dew margin 3.7F and 0.1 dew-risk h. Water 39 gal vs 9 gal 7d average; cost, gas/electric usage unavailable. Realized dryout read was available with 16 episodes: 8 ineffective and 8 insufficient evidence, none blocked; safety gate passed, but no proven effective dry-out, and zero hold admissions does not establish complete daylight coverage. Daily observed-minute evidence had 95.97% temperature coverage but no eligible VPD rows; no physical crop outcome or consumed-target proof. No causal attribution or durable lesson. Score: 4/10
Hypothesis
Testing: No causal experiment; test restrained overnight wetting with a live-edge-only sunrise handoff. Expected outcome: Keep overnight VPD-low stress below 0.5 nominal h and dew-risk at 0; make modest assist available near the live high edge by 10:00 if measured demand develops. No crop or cost benefit assumed.
Setpoints
Monday November 09
Primary crop-band changes:
| Time | Values | Note |
|---|---|---|
| 00:00 | hyst 0.2565 | Cold night and VPD-low yesterday: suppress wetting unless li |
| 04:00 | hyst 0.2565 | Pre-dawn remains cold; retain heat and avoid forecast-only w |
| 07:00 | hyst 0.2565 | Begin a restrained sunrise ramp; avoid repeating morning ove |
| 10:00 | hyst 0.2565 | Handoff to near-edge assist only as the dry ramp arrives; ma |
Tactical tunable changes:
| Time | Values | Note |
|---|---|---|
| 00:00 | s2 1.98; cool_exit 2.14; all_fans 0; dw_stress 0; engage 1.1; all 1.25; pulse 30; gap 60; wt 1.32 | Cold night and VPD-low yesterday: suppress wetting unless li |
| 04:00 | s2 1.98; cool_exit 2.14; all_fans 0; dw_stress 0; engage 1.1; all 1.25; pulse 30; gap 60; wt 1.32 | Pre-dawn remains cold; retain heat and avoid forecast-only w |
| 07:00 | s2 1.8625; cool_exit 2.14; all_fans 0; dw_stress 0; engage 1.05; all 1.2; pulse 30; gap 52.5; wt 1.4133333333333333 | Begin a restrained sunrise ramp; avoid repeating morning ove |
| 10:00 | s2 1.8025000000000002; cool_exit 2.14; all_fans 0; dw_stress 0; engage 0.9500000000000001; all 1.15; pulse 30; gap 37.5; wt 1.5866666666666664 | Handoff to near-edge assist only as the dry ramp arrives; ma |
Changed secondary parameters:
| Time | Parameter | Change |
|---|---|---|
| 00:00 | band_track_fraction | initial 0 |
| 00:00 | cold_vent_guard_delta_f | initial 12 |
| 00:00 | cool_stage2_exit_hysteresis_f | initial 1 |
| 00:00 | direct_wet_stress_min_dew_margin_f | initial 10 |
| 00:00 | direct_wet_stress_vpd_margin_kpa | initial 0.2 |
| 00:00 | dwell_gate_ms | initial 300000 |
| 00:00 | enthalpy_close | initial 1 |
| 00:00 | enthalpy_open | initial -2 |
| 00:00 | fog_escalation_kpa | initial 0.4 |
| 00:00 | heat_hysteresis | initial 1 |
| 00:00 | min_fog_off_s | initial 102 |
| 00:00 | min_fog_on_s | initial 48 |
| 00:00 | mist_backoff_s | initial 600 |
| 00:00 | mist_max_closed_vent_s | initial 600 |
| 00:00 | mist_thermal_relief_s | initial 90 |
| 00:00 | mister_all_delay_s | initial 102 |
| 00:00 | mister_engage_delay_s | initial 51 |
| 00:00 | mister_water_budget_gal | initial 120 |
| 00:00 | night_vpd_bias_kpa | initial 0 |
| 00:00 | outdoor_staleness_max_s | initial 600 |
| 00:00 | sw_dwell_gate_enabled | initial 1 |
| 00:00 | sw_fog_closes_vent | initial 1 |
| 00:00 | sw_mister_closes_vent | initial 0 |
| 00:00 | sw_summer_vent_enabled | initial 1 |
| 00:00 | temp_hysteresis | initial 2.14 |
| 00:00 | vent_exchange_fraction | initial 0.3 |
| 00:00 | vent_prefer_dp_delta_f | initial 5 |
| 00:00 | vent_prefer_temp_delta_f | initial 8 |
| 00:00 | vpd_watch_dwell_s | initial 75 |
| 07:00 | cold_vent_guard_delta_f | 12 → 11 |
| 07:00 | direct_wet_stress_vpd_margin_kpa | 0.2 → 0.15 |
| 07:00 | fog_escalation_kpa | 0.4 → 0.35 |
| 07:00 | min_fog_off_s | 102 → 90 |
| 07:00 | min_fog_on_s | 48 → 52.5 |
| 07:00 | vent_prefer_dp_delta_f | 5 → 4 |
| 07:00 | vent_prefer_temp_delta_f | 8 → 7 |
| 10:00 | cold_vent_guard_delta_f | 11 → 10 |
| 10:00 | direct_wet_stress_vpd_margin_kpa | 0.15 → 0.05 |
| 10:00 | fog_escalation_kpa | 0.35 → 0.3 |
| 10:00 | min_fog_off_s | 90 → 66 |
| 10:00 | min_fog_on_s | 52.5 → 61.5 |
| 10:00 | vent_prefer_temp_delta_f | 7 → 6 |
🌅 Morning Cycle (2:05 AM) — iris-20261109-0200
validated
4/10
band_track_fraction, cold_vent_guard_delta_f, cool_exit_hysteresis_f, cool_stage2_exit_hysteresis_f, cool_stage2_over_high_f, direct_wet_stress_min_dew_margin_f, direct_wet_stress_vpd_margin_kpa, dwell_gate_ms ...
Reflection
Validating previous cycle: iris-20261108-1655
Result: Plan iris-20261109-0200 governed only a short partial window (~0.193 day, about 4.6 h) before the sunrise replacement. Its scoped window scorecard was planner_score 71.6 with contract-2 binary both-axis/temp/VPD 37.9%/96.1%/39.8%; nominal stress 1.06 h, including 0.06 h cold and 1.00 h VPD-low, no VPD-high or heat stress, and no dew-risk. This shows temperature was contained while VPD-low remained the limiting axis, but does not validate the plan’s full-horizon hypothesis or establish causal efficacy. Coverage, consumed targets, resource costs, and physical crop outcomes are unavailable; current deviation read shows outdoor temp has warmed, with the refreshed forecast now near observed and tonight’s 35F frost risk still intact. Score: 4/10
Hypothesis
Testing: Observe low-wet overnight plus safe dry-air exchange; observational only, not a causal experiment. Expected outcome: On the first full governed day: nominal VPD-low stress ⇐8h (recent 9.17–12.42h/day), dp_risk ⇐0.1h, binary temp compliance >=95%, VPD-high ⇐1h. Coverage and targets remain unverified; no crop or cost benefit claimed.
Setpoints
Monday November 09
Primary crop-band changes:
| Time | Values | Note |
|---|---|---|
| 02:00 | hyst 0.24825000000000003 | Fresh air is 59.8F/0.66 kPa with 12.9F dew margin; preserve |
| 08:00 | hyst 0.24825000000000003 | Clear Monday warms to 69F; outdoor VPD peaks near 2.05. Allo |
Tactical tunable changes:
| Time | Values | Note |
|---|---|---|
| 02:00 | s2 1.8625; cool_exit 1.96; all_fans 0; dw_stress 0; engage 1.1; all 1.25; pulse 30; gap 52.5; wt 1.4 | Fresh air is 59.8F/0.66 kPa with 12.9F dew margin; preserve |
| 08:00 | s2 1.7825; cool_exit 1.96; all_fans 0; dw_stress 0; engage 1; all 1.15; pulse 30; gap 41.25; wt 1.5666666666666669 | Clear Monday warms to 69F; outdoor VPD peaks near 2.05. Allo |
Tuesday November 10
Primary crop-band changes:
| Time | Values | Note |
|---|---|---|
| 07:00 | hyst 0.24825000000000003 | Tue dawn falls to 36F; retain heat-safe restraint, then keep |
Tactical tunable changes:
| Time | Values | Note |
|---|---|---|
| 07:00 | s2 1.8675000000000002; cool_exit 1.96; all_fans 0; dw_stress 0; engage 1; all 1.15; pulse 30; gap 45; wt 1.52 | Tue dawn falls to 36F; retain heat-safe restraint, then keep |
Wednesday November 11
Primary crop-band changes:
| Time | Values | Note |
|---|---|---|
| 07:00 | hyst 0.24825000000000003 | Wed turns clear and dry to 67F/1.97 kPa outdoor VPD; retain |
Tactical tunable changes:
| Time | Values | Note |
|---|---|---|
| 07:00 | s2 1.7825; cool_exit 1.96; all_fans 0; dw_stress 0; engage 1; all 1.15; pulse 30; gap 41.25; wt 1.5666666666666669 | Wed turns clear and dry to 67F/1.97 kPa outdoor VPD; retain |
Thursday November 12
Primary crop-band changes:
| Time | Values | Note |
|---|---|---|
| 01:00 | hyst 0.24825000000000003 | Return to restrained pre-dawn wetting; resume daytime assist |
Tactical tunable changes:
| Time | Values | Note |
|---|---|---|
| 01:00 | s2 1.8975; cool_exit 1.96; all_fans 0; dw_stress 0; engage 1.1; all 1.25; pulse 30; gap 52.5; wt 1.4 | Return to restrained pre-dawn wetting; resume daytime assist |
Changed secondary parameters:
| Time | Parameter | Change |
|---|---|---|
| 02:00 | band_track_fraction | initial 0 |
| 02:00 | cold_vent_guard_delta_f | initial 12 |
| 02:00 | cool_stage2_exit_hysteresis_f | initial 1 |
| 02:00 | direct_wet_stress_min_dew_margin_f | initial 8 |
| 02:00 | direct_wet_stress_vpd_margin_kpa | initial 0.2 |
| 02:00 | dwell_gate_ms | initial 270000 |
| 02:00 | enthalpy_close | initial 1 |
| 02:00 | enthalpy_open | initial -2 |
| 02:00 | fog_escalation_kpa | initial 0.35 |
| 02:00 | heat_hysteresis | initial 1 |
| 02:00 | min_fog_off_s | initial 90 |
| 02:00 | min_fog_on_s | initial 52.5 |
| 02:00 | mist_backoff_s | initial 600 |
| 02:00 | mist_max_closed_vent_s | initial 600 |
| 02:00 | mist_thermal_relief_s | initial 90 |
| 02:00 | mister_all_delay_s | initial 93 |
| 02:00 | mister_engage_delay_s | initial 46.5 |
| 02:00 | mister_water_budget_gal | initial 120 |
| 02:00 | night_vpd_bias_kpa | initial 0 |
| 02:00 | outdoor_staleness_max_s | initial 600 |
| 02:00 | sw_dwell_gate_enabled | initial 1 |
| 02:00 | sw_fog_closes_vent | initial 1 |
| 02:00 | sw_mister_closes_vent | initial 0 |
| 02:00 | sw_summer_vent_enabled | initial 1 |
| 02:00 | temp_hysteresis | initial 1.96 |
| 02:00 | vent_exchange_fraction | initial 0.3 |
| 02:00 | vent_prefer_dp_delta_f | initial 3 |
| 02:00 | vent_prefer_temp_delta_f | initial 8 |
| 02:00 | vpd_watch_dwell_s | initial 67.5 |
| 08:00 | cold_vent_guard_delta_f | 12 → 9 |
| 08:00 | direct_wet_stress_vpd_margin_kpa | 0.2 → 0.1 |
| 08:00 | fog_escalation_kpa | 0.35 → 0.3 |
| 08:00 | min_fog_off_s | 90 → 72 |
| 08:00 | min_fog_on_s | 52.5 → 59.25 |
| 08:00 | vent_prefer_temp_delta_f | 8 → 5 |
| 07:00 | cold_vent_guard_delta_f | 9 → 11 |
| 07:00 | min_fog_off_s | 72 → 78 |
| 07:00 | min_fog_on_s | 59.25 → 57 |
| 07:00 | vent_prefer_temp_delta_f | 5 → 7 |
| 07:00 | cold_vent_guard_delta_f | 11 → 9 |
| 07:00 | fog_escalation_kpa | 0.3 → 0.25 |
| 07:00 | min_fog_off_s | 78 → 72 |
| 07:00 | min_fog_on_s | 57 → 59.25 |
| 07:00 | vent_prefer_temp_delta_f | 7 → 5 |
| 01:00 | cold_vent_guard_delta_f | 9 → 13 |
| 01:00 | direct_wet_stress_vpd_margin_kpa | 0.1 → 0.2 |
| 01:00 | fog_escalation_kpa | 0.25 → 0.35 |
| 01:00 | min_fog_off_s | 72 → 90 |
| 01:00 | min_fog_on_s | 59.25 → 52.5 |
| 01:00 | vent_prefer_temp_delta_f | 5 → 9 |
🌅 Morning Cycle (6:42 AM) — iris-20261109-0640
validated
2/10
band_track_fraction, cold_vent_guard_delta_f, cool_exit_hysteresis_f, cool_stage2_exit_hysteresis_f, cool_stage2_over_high_f, direct_wet_stress_min_dew_margin_f, direct_wet_stress_vpd_margin_kpa, dwell_gate_ms ...
Reflection
Validating previous cycle: iris-20261108-1655
Result: This plan governed only about 2.2 hours (06:42-08:52 local), ending before its forecast dry midday window. Its scoped window scorecard shows 97.5% binary temp compliance, 61.8% VPD compliance, about 0.62 nominal stress hours (0.56 VPD-low, 0.04 cold, 0.01 VPD-high); no usable evidence for the predicted midday VPD-high mitigation or overnight cold posture. Outdoor peak was 67.7F versus 70F predicted; outdoor RH proxy minimum was 53% versus 15% predicted; solar peak 584 versus 508 W/m2; cloud average unavailable. Very short, forecast-mismatched window; no effectiveness or causal crop/resource outcome established. Score: 2/10
Hypothesis
Testing: Observational test: protect the cold dawn from wet carryover, then enable modest band-coupled assist through the clear dry ramp; review VPD, dew and guardrail evidence without causal claims. Expected outcome: Today: hold temp compliance near the recent 97% diagnostic, keep VPD-high ⇐1h and dew-risk ⇐0.1h, and reduce VPD-low hours from Nov 8’s 12.42h. Resource and physical crop outcomes remain unverified.
Conditions
70.0°F
15.0%
508.0 W/m²
0.0%
Nov 8 contract-2 score 76.2; temp/VPD binary 97.2%/47.6%, VPD-low 12.42h, minimum dew margin 3.7F; cost unavailable, water 39 gal vs 9 gal 7d average. Current house 64.2F/0.88kPa with 15.5F dew margin. Clear dry ramp reaches 70F, 15% RH and 2.09kPa outdoor VPD; next dawn low 36F. Prior completed short window had 0.65h VPD-low; 14 guardrail events, 7 held, limit attribution.
Expected stress windows
Enable modest band-coupled mist/fog only on live demand; keep an 8F dew floor.
Preserve heat-first posture and 10F dew floor; avoid cold-air exchange without safe advantage.
Parameter rationale
Make wet assist available near the live high edge; keep forecast-driven VPD-high stress at or below 1h.
Allow conditional daytime escalation while retaining an 8F dew floor and targeting dp-risk no higher than 0.1h.
Setpoints
Monday November 09
Primary crop-band changes:
| Time | Values | Note |
|---|---|---|
| 06:39 | hyst 0.19675 | Cold dawn; keep wetting edge-gated and protect dew margin wh |
| 09:00 | hyst 0.19675 | Clear dry ramp starts; make modest band-relative wet assist |
| 13:00 | hyst 0.19675 | Peak dry-air period; preserve live-edge moisture assist with |
| 16:30 | hyst 0.19675 | Afternoon decline; retain modest assist until measured VPD r |
| 19:00 | hyst 0.19675 | Evening/cold-night handoff; keep low-duty edge assist and ti |
Tactical tunable changes:
| Time | Values | Note |
|---|---|---|
| 06:39 | s2 1.8925; cool_exit 1.78; all_fans 0; dw_stress 0; engage 1; all 1.2; pulse 30; gap 60; wt 1.3333333333333333 | Cold dawn; keep wetting edge-gated and protect dew margin wh |
| 09:00 | s2 1.7800000000000002; cool_exit 1.78; all_fans 0; dw_stress 0; engage 0.9500000000000001; all 1.15; pulse 30; gap 45; wt 1.5333333333333332 | Clear dry ramp starts; make modest band-relative wet assist |
| 13:00 | s2 1.6800000000000002; cool_exit 1.78; all_fans 0; dw_stress 0; engage 0.9500000000000001; all 1.15; pulse 37.5; gap 37.5; wt 1.6666666666666665 | Peak dry-air period; preserve live-edge moisture assist with |
| 16:30 | s2 1.8325; cool_exit 1.78; all_fans 0; dw_stress 0; engage 0.9500000000000001; all 1.15; pulse 30; gap 45; wt 1.5333333333333332 | Afternoon decline; retain modest assist until measured VPD r |
| 19:00 | s2 1.965; cool_exit 1.78; all_fans 0; dw_stress 0; engage 0.9500000000000001; all 1.15; pulse 30; gap 56.25; wt 1.4 | Evening/cold-night handoff; keep low-duty edge assist and ti |
Changed secondary parameters:
| Time | Parameter | Change |
|---|---|---|
| 06:39 | band_track_fraction | initial 0 |
| 06:39 | cold_vent_guard_delta_f | initial 12 |
| 06:39 | cool_stage2_exit_hysteresis_f | initial 1 |
| 06:39 | direct_wet_stress_min_dew_margin_f | initial 10 |
| 06:39 | direct_wet_stress_vpd_margin_kpa | initial 0.1 |
| 06:39 | dwell_gate_ms | initial 240000 |
| 06:39 | enthalpy_close | initial 1 |
| 06:39 | enthalpy_open | initial -2 |
| 06:39 | fog_escalation_kpa | initial 0.35 |
| 06:39 | heat_hysteresis | initial 1 |
| 06:39 | min_fog_off_s | initial 102 |
| 06:39 | min_fog_on_s | initial 48 |
| 06:39 | mist_backoff_s | initial 600 |
| 06:39 | mist_max_closed_vent_s | initial 600 |
| 06:39 | mist_thermal_relief_s | initial 90 |
| 06:39 | mister_all_delay_s | initial 84 |
| 06:39 | mister_engage_delay_s | initial 42 |
| 06:39 | mister_water_budget_gal | initial 120 |
| 06:39 | night_vpd_bias_kpa | initial 0 |
| 06:39 | outdoor_staleness_max_s | initial 600 |
| 06:39 | sw_dwell_gate_enabled | initial 1 |
| 06:39 | sw_fog_closes_vent | initial 1 |
| 06:39 | sw_mister_closes_vent | initial 0 |
| 06:39 | sw_summer_vent_enabled | initial 1 |
| 06:39 | temp_hysteresis | initial 1.78 |
| 06:39 | vent_exchange_fraction | initial 0.3 |
| 06:39 | vent_prefer_dp_delta_f | initial 3 |
| 06:39 | vent_prefer_temp_delta_f | initial 8 |
| 06:39 | vpd_watch_dwell_s | initial 60 |
| 09:00 | direct_wet_stress_min_dew_margin_f | 10 → 8 |
| 09:00 | direct_wet_stress_vpd_margin_kpa | 0.1 → 0.05 |
| 09:00 | fog_escalation_kpa | 0.35 → 0.25 |
| 09:00 | min_fog_off_s | 102 → 78 |
| 09:00 | min_fog_on_s | 48 → 57 |
| 13:00 | min_fog_off_s | 78 → 66 |
| 13:00 | min_fog_on_s | 57 → 61.5 |
| 16:30 | direct_wet_stress_min_dew_margin_f | 8 → 9 |
| 16:30 | fog_escalation_kpa | 0.25 → 0.3 |
| 16:30 | min_fog_off_s | 66 → 78 |
| 16:30 | min_fog_on_s | 61.5 → 57 |
| 19:00 | direct_wet_stress_min_dew_margin_f | 9 → 10 |
| 19:00 | fog_escalation_kpa | 0.3 → 0.35 |
| 19:00 | min_fog_off_s | 78 → 96 |
| 19:00 | min_fog_on_s | 57 → 50.25 |
🌅 Morning Cycle (8:52 AM) — iris-20261109-0850
validated
2/10
band_track_fraction, cold_vent_guard_delta_f, cool_exit_hysteresis_f, cool_stage2_exit_hysteresis_f, cool_stage2_over_high_f, direct_wet_stress_min_dew_margin_f, direct_wet_stress_vpd_margin_kpa, dwell_gate_ms ...
Reflection
Validating previous cycle: iris-20261109-0015
Previous hypothesis: Nov 8 contract-2 score was 76.4 (binary temp 97.2%, VPD 47.6%; 12.42 nominal VPD-low h; minimum dew margin 3.7°F and 0.1 dew-risk h; resource terms unavailable). Nov 9 begins at 60.4°F/0.55 kPa with a 10°F dew margin and heat1 on. Keep wetting restrained through the 39–41°F pre-dawn, then reopen only near the live VPD high edge as clear air warms and dries to 56°F/31% RH and 1.06 kPa outdoor VPD by 10:00. Preserve a 10°F dew floor and stable transitions. Outdoor forecast is forcing, not indoor exposure; no crop or cost benefit is assumed. The two short deviation windows scored 4 and 3; deterministic anchors were unavailable. Result: This replacement governed about 1.8 hours (08:52-10:38 local), ending before the predicted afternoon dry/VPD-high window and before the forecast cold night. Its scoped scorecard again reports 97.5% binary temp compliance, 61.8% VPD compliance, about 0.50 nominal stress hours (0.46 VPD-low, 0.03 cold, 0.01 VPD-high). Outdoor conditions did not confirm the forecast dry/clear setup (RH proxy minimum 53% versus 15%; cloud/solar coverage incomplete); the cloud deviation later at 16:49 cannot be attributed to this short window. No meaningful test of the full plan or causal benefit; resource costs and crop outcome unavailable. Score: 2/10
Hypothesis
Testing: Forecast-deviation hold: keep forecast offsets neutral, preserve live-gated moisture and evaluate against observed climate; no causal efficacy claim. Expected outcome: Avoid a plan change based solely on the stale warm-observation miss; protect the crop corridor and cold nights, with wet assist only on measured VPD demand. Costs and crop efficacy remain unverified.
Setpoints
Monday November 09
Primary crop-band changes:
| Time | Values | Note |
|---|---|---|
| 08:50 | hyst 0.167 | Deviation is explained by forecast catch-up; preserve neutra |
| 17:00 | hyst 0.177 | Taper wetting as solar falls; protect dew margin ahead of th |
Tactical tunable changes:
| Time | Values | Note |
|---|---|---|
| 08:50 | s2 1.745; cool_exit 1.78; all_fans 0; dw_stress 0; engage 0.9500000000000001; all 1.15; pulse 30; gap 45; wt 1.5333333333333332 | Deviation is explained by forecast catch-up; preserve neutra |
| 17:00 | s2 1.775; cool_exit 1.96; all_fans 0; dw_stress 0; engage 1.05; all 1.25; pulse 30; gap 52.5; wt 1.4 | Taper wetting as solar falls; protect dew margin ahead of th |
Tuesday November 10
Primary crop-band changes:
| Time | Values | Note |
|---|---|---|
| 07:00 | hyst 0.177 | Cloudy 35°F dawn: retain heat-first, dew-safe posture and av |
| 10:00 | hyst 0.167 | Reopen modest wet assist only around the live crop VPD edge |
| 19:00 | hyst 0.177 | Taper wetting for the cold clear night; preserve dew margin |
Tactical tunable changes:
| Time | Values | Note |
|---|---|---|
| 07:00 | s2 1.775; cool_exit 1.96; all_fans 0; dw_stress 0; engage 1.05; all 1.25; pulse 30; gap 52.5; wt 1.4 | Cloudy 35°F dawn: retain heat-first, dew-safe posture and av |
| 10:00 | s2 1.745; cool_exit 1.78; all_fans 0; dw_stress 0; engage 0.9500000000000001; all 1.15; pulse 30; gap 45; wt 1.5333333333333332 | Reopen modest wet assist only around the live crop VPD edge |
| 19:00 | s2 1.775; cool_exit 1.96; all_fans 0; dw_stress 0; engage 1.05; all 1.25; pulse 30; gap 52.5; wt 1.4 | Taper wetting for the cold clear night; preserve dew margin |
Wednesday November 11
Primary crop-band changes:
| Time | Values | Note |
|---|---|---|
| 09:00 | hyst 0.167 | Keep response live-gated through the forecast dry ramp; no a |
| 17:00 | hyst 0.177 | Return to conservative wetting after the afternoon; hold mar |
Tactical tunable changes:
| Time | Values | Note |
|---|---|---|
| 09:00 | s2 1.745; cool_exit 1.78; all_fans 0; dw_stress 0; engage 0.9500000000000001; all 1.15; pulse 30; gap 45; wt 1.5333333333333332 | Keep response live-gated through the forecast dry ramp; no a |
| 17:00 | s2 1.775; cool_exit 1.96; all_fans 0; dw_stress 0; engage 1.05; all 1.25; pulse 30; gap 52.5; wt 1.4 | Return to conservative wetting after the afternoon; hold mar |
Changed secondary parameters:
| Time | Parameter | Change |
|---|---|---|
| 08:50 | band_track_fraction | initial 0 |
| 08:50 | cold_vent_guard_delta_f | initial 12 |
| 08:50 | cool_stage2_exit_hysteresis_f | initial 1 |
| 08:50 | direct_wet_stress_min_dew_margin_f | initial 8 |
| 08:50 | direct_wet_stress_vpd_margin_kpa | initial 0.05 |
| 08:50 | dwell_gate_ms | initial 240000 |
| 08:50 | enthalpy_close | initial 1 |
| 08:50 | enthalpy_open | initial -2 |
| 08:50 | fog_escalation_kpa | initial 0.3 |
| 08:50 | heat_hysteresis | initial 1 |
| 08:50 | min_fog_off_s | initial 78 |
| 08:50 | min_fog_on_s | initial 57 |
| 08:50 | mist_backoff_s | initial 600 |
| 08:50 | mist_max_closed_vent_s | initial 600 |
| 08:50 | mist_thermal_relief_s | initial 90 |
| 08:50 | mister_all_delay_s | initial 84 |
| 08:50 | mister_engage_delay_s | initial 42 |
| 08:50 | mister_water_budget_gal | initial 120 |
| 08:50 | night_vpd_bias_kpa | initial 0 |
| 08:50 | outdoor_staleness_max_s | initial 600 |
| 08:50 | sw_dwell_gate_enabled | initial 1 |
| 08:50 | sw_fog_closes_vent | initial 1 |
| 08:50 | sw_mister_closes_vent | initial 0 |
| 08:50 | sw_summer_vent_enabled | initial 1 |
| 08:50 | temp_hysteresis | initial 1.78 |
| 08:50 | vent_exchange_fraction | initial 0.3 |
| 08:50 | vent_prefer_dp_delta_f | initial 3 |
| 08:50 | vent_prefer_temp_delta_f | initial 8 |
| 08:50 | vpd_watch_dwell_s | initial 60 |
| 17:00 | direct_wet_stress_min_dew_margin_f | 8 → 10 |
| 17:00 | direct_wet_stress_vpd_margin_kpa | 0.05 → 0.15 |
| 17:00 | dwell_gate_ms | 240000 → 270000 |
| 17:00 | fog_escalation_kpa | 0.3 → 0.4 |
| 17:00 | min_fog_off_s | 78 → 90 |
| 17:00 | min_fog_on_s | 57 → 52.5 |
| 17:00 | mister_all_delay_s | 84 → 93 |
| 17:00 | mister_engage_delay_s | 42 → 46.5 |
| 17:00 | temp_hysteresis | 1.78 → 1.96 |
| 17:00 | vpd_watch_dwell_s | 60 → 67.5 |
| 10:00 | direct_wet_stress_min_dew_margin_f | 10 → 8 |
| 10:00 | direct_wet_stress_vpd_margin_kpa | 0.15 → 0.05 |
| 10:00 | dwell_gate_ms | 270000 → 240000 |
| 10:00 | fog_escalation_kpa | 0.4 → 0.3 |
| 10:00 | min_fog_off_s | 90 → 78 |
| 10:00 | min_fog_on_s | 52.5 → 57 |
| 10:00 | mister_all_delay_s | 93 → 84 |
| 10:00 | mister_engage_delay_s | 46.5 → 42 |
| 10:00 | temp_hysteresis | 1.96 → 1.78 |
| 10:00 | vpd_watch_dwell_s | 67.5 → 60 |
| 19:00 | direct_wet_stress_min_dew_margin_f | 8 → 10 |
| 19:00 | direct_wet_stress_vpd_margin_kpa | 0.05 → 0.15 |
| 19:00 | dwell_gate_ms | 240000 → 270000 |
| 19:00 | fog_escalation_kpa | 0.3 → 0.45 |
| 19:00 | min_fog_off_s | 78 → 90 |
| 19:00 | min_fog_on_s | 57 → 52.5 |
| 19:00 | mister_all_delay_s | 84 → 93 |
| 19:00 | mister_engage_delay_s | 42 → 46.5 |
| 19:00 | temp_hysteresis | 1.78 → 1.96 |
| 19:00 | vpd_watch_dwell_s | 60 → 67.5 |
| 09:00 | direct_wet_stress_min_dew_margin_f | 10 → 8 |
| 09:00 | direct_wet_stress_vpd_margin_kpa | 0.15 → 0.05 |
| 09:00 | dwell_gate_ms | 270000 → 240000 |
| 09:00 | fog_escalation_kpa | 0.45 → 0.3 |
| 09:00 | min_fog_off_s | 90 → 78 |
| 09:00 | min_fog_on_s | 52.5 → 57 |
| 09:00 | mister_all_delay_s | 93 → 84 |
| 09:00 | mister_engage_delay_s | 46.5 → 42 |
| 09:00 | temp_hysteresis | 1.96 → 1.78 |
| 09:00 | vpd_watch_dwell_s | 67.5 → 60 |
| 17:00 | direct_wet_stress_min_dew_margin_f | 8 → 10 |
| 17:00 | direct_wet_stress_vpd_margin_kpa | 0.05 → 0.15 |
| 17:00 | dwell_gate_ms | 240000 → 270000 |
| 17:00 | fog_escalation_kpa | 0.3 → 0.4 |
| 17:00 | min_fog_off_s | 78 → 90 |
| 17:00 | min_fog_on_s | 57 → 52.5 |
| 17:00 | mister_all_delay_s | 84 → 93 |
| 17:00 | mister_engage_delay_s | 42 → 46.5 |
| 17:00 | temp_hysteresis | 1.78 → 1.96 |
| 17:00 | vpd_watch_dwell_s | 60 → 67.5 |
☀️ Midday Cycle (10:38 AM) — iris-20261109-1034
validated
4/10
band_track_fraction, cold_vent_guard_delta_f, cool_exit_hysteresis_f, cool_stage2_exit_hysteresis_f, cool_stage2_over_high_f, direct_wet_stress_min_dew_margin_f, direct_wet_stress_vpd_margin_kpa, dwell_gate_ms ...
Reflection
Validating previous cycle: iris-20261109-0200
Previous hypothesis: Nov 2–8 contract-2 planner_score averaged 76.5; binary temp compliance stayed 94–99% and VPD 47–62%, while nominal VPD-low stress dominated at 9.17–12.42h/day. VPD-high stayed ⇐0.67h and dp-risk was 0–0.2h; resource terms were unavailable. Completed iris-20261108-1655 scored 3/10 vs anchor 1: its 7.4h replacement window had 0.53h VPD-low and no recorded dew-risk, but ended before most of its predicted overnight window; 124 VPD-high guardrail requests (89 held) limit attribution. For the next 72h, protect cold nights, reduce unnecessary wet carryover, and permit dry-air exchange only with safe temperature/dewpoint advantage while keeping modest live-edge daytime assist. Predict ⇐8h VPD-low, ⇐0.1h dp-risk, >=95% temp compliance and ⇐1h VPD-high on the first full governed day; these are diagnostics, not crop or causal outcomes. Result: Plan window 0.259 days (~6.2h): contract-2 historical score 76.6; binary temp/VPD compliance 97.9%/60.4%. Nominal stress was 0 heat, 0.13h cold, 0.02h VPD-high, 2.44h VPD-low, 0 dew-risk. Temperature containment and low VPD-high exposure were favorable, but VPD-low was the main miss and the forecast/conditions summary described a nowcast mismatch; the window ended before the frost-night portion. No resource-cost or physical crop outcome is available. Historical desired bands, coverage, and consumed targets are unverified, so efficacy/causality is limited. Score: 4/10
Hypothesis
Setpoints
Monday November 09
Primary crop-band changes:
| Time | Values | Note |
|---|---|---|
| 10:30 | hyst 0.1375 | Indoor VPD is just above band; allow low-duty assist only at |
| 17:00 | hyst 0.1375 | Taper evening wet duty; retain a short live-edge recovery sh |
Tactical tunable changes:
| Time | Values | Note |
|---|---|---|
| 10:30 | s2 1.7725000000000002; cool_exit 1.6; all_fans 0; dw_stress 1; engage 0.9500000000000001; all 1.15; pulse 33.75; gap 30; wt 1.7000000000000002 | Indoor VPD is just above band; allow low-duty assist only at |
| 17:00 | s2 1.8900000000000001; cool_exit 1.6; all_fans 0; dw_stress 1; engage 0.9500000000000001; all 1.15; pulse 33.75; gap 37.5; wt 1.7 | Taper evening wet duty; retain a short live-edge recovery sh |
Tuesday November 10
Primary crop-band changes:
| Time | Values | Note |
|---|---|---|
| 09:00 | hyst 0.1375 | After 35°F frost, keep dawn wetting live-gated; enable modes |
| 17:00 | hyst 0.1375 | Reduce wet carryover into the cold evening; keep only limite |
Tactical tunable changes:
| Time | Values | Note |
|---|---|---|
| 09:00 | s2 1.86; cool_exit 1.6; all_fans 0; dw_stress 1; engage 0.9500000000000001; all 1.15; pulse 33.75; gap 30; wt 1.7000000000000002 | After 35°F frost, keep dawn wetting live-gated; enable modes |
| 17:00 | s2 1.8900000000000001; cool_exit 1.6; all_fans 0; dw_stress 1; engage 0.9500000000000001; all 1.15; pulse 33.75; gap 37.5; wt 1.7 | Reduce wet carryover into the cold evening; keep only limite |
Wednesday November 11
Primary crop-band changes:
| Time | Values | Note |
|---|---|---|
| 09:00 | hyst 0.1375 | Modest live-edge assist for the dry ramp; keep offsets neutr |
| 17:00 | hyst 0.1375 | Taper at dusk to limit VPD-low and dew-risk carryover into t |
Tactical tunable changes:
| Time | Values | Note |
|---|---|---|
| 09:00 | s2 1.7725000000000002; cool_exit 1.6; all_fans 0; dw_stress 1; engage 0.9500000000000001; all 1.15; pulse 33.75; gap 30; wt 1.7000000000000002 | Modest live-edge assist for the dry ramp; keep offsets neutr |
| 17:00 | s2 1.8900000000000001; cool_exit 1.6; all_fans 0; dw_stress 1; engage 0.9500000000000001; all 1.15; pulse 33.75; gap 37.5; wt 1.7 | Taper at dusk to limit VPD-low and dew-risk carryover into t |
Thursday November 12
Primary crop-band changes:
| Time | Values | Note |
|---|---|---|
| 08:00 | hyst 0.1375 | Keep wet assist modest and live-gated as the 43°F morning wa |
Tactical tunable changes:
| Time | Values | Note |
|---|---|---|
| 08:00 | s2 1.86; cool_exit 1.6; all_fans 0; dw_stress 1; engage 0.9500000000000001; all 1.15; pulse 33.75; gap 30; wt 1.7000000000000002 | Keep wet assist modest and live-gated as the 43°F morning wa |
Changed secondary parameters:
| Time | Parameter | Change |
|---|---|---|
| 10:30 | band_track_fraction | initial 0 |
| 10:30 | cold_vent_guard_delta_f | initial 8 |
| 10:30 | cool_stage2_exit_hysteresis_f | initial 1 |
| 10:30 | direct_wet_stress_min_dew_margin_f | initial 8 |
| 10:30 | direct_wet_stress_vpd_margin_kpa | initial 0.05 |
| 10:30 | dwell_gate_ms | initial 210000 |
| 10:30 | enthalpy_close | initial 1 |
| 10:30 | enthalpy_open | initial -2 |
| 10:30 | fog_escalation_kpa | initial 0.2 |
| 10:30 | heat_hysteresis | initial 1 |
| 10:30 | min_fog_off_s | initial 54 |
| 10:30 | min_fog_on_s | initial 66 |
| 10:30 | mist_backoff_s | initial 600 |
| 10:30 | mist_max_closed_vent_s | initial 600 |
| 10:30 | mist_thermal_relief_s | initial 90 |
| 10:30 | mister_all_delay_s | initial 75 |
| 10:30 | mister_engage_delay_s | initial 37.5 |
| 10:30 | mister_water_budget_gal | initial 120 |
| 10:30 | night_vpd_bias_kpa | initial 0 |
| 10:30 | outdoor_staleness_max_s | initial 600 |
| 10:30 | sw_dwell_gate_enabled | initial 1 |
| 10:30 | sw_fog_closes_vent | initial 1 |
| 10:30 | sw_mister_closes_vent | initial 0 |
| 10:30 | sw_summer_vent_enabled | initial 1 |
| 10:30 | temp_hysteresis | initial 1.6 |
| 10:30 | vent_exchange_fraction | initial 0.3 |
| 10:30 | vent_prefer_dp_delta_f | initial 3 |
| 10:30 | vent_prefer_temp_delta_f | initial 4 |
| 10:30 | vpd_watch_dwell_s | initial 52.5 |
| 17:00 | direct_wet_stress_min_dew_margin_f | 8 → 10 |
| 17:00 | min_fog_off_s | 54 → 66 |
| 17:00 | min_fog_on_s | 66 → 61.5 |
| 09:00 | min_fog_off_s | 66 → 54 |
| 09:00 | min_fog_on_s | 61.5 → 66 |
| 17:00 | min_fog_off_s | 54 → 66 |
| 17:00 | min_fog_on_s | 66 → 61.5 |
| 09:00 | direct_wet_stress_min_dew_margin_f | 10 → 8 |
| 09:00 | min_fog_off_s | 66 → 54 |
| 09:00 | min_fog_on_s | 61.5 → 66 |
| 17:00 | direct_wet_stress_min_dew_margin_f | 8 → 10 |
| 17:00 | min_fog_off_s | 54 → 66 |
| 17:00 | min_fog_on_s | 66 → 61.5 |
| 08:00 | min_fog_off_s | 66 → 54 |
| 08:00 | min_fog_on_s | 61.5 → 66 |
🌆 Evening Cycle (4:52 PM) — iris-20261109-1649
validated
3/10
band_track_fraction, cold_vent_guard_delta_f, cool_exit_hysteresis_f, cool_stage2_exit_hysteresis_f, cool_stage2_over_high_f, direct_wet_stress_min_dew_margin_f, direct_wet_stress_vpd_margin_kpa, dwell_gate_ms ...
Reflection
Validating previous cycle: iris-20261109-0850
Previous hypothesis: Deviation +13.83°F was outdoor temperature (observed 50.8°F vs stale 37°F forecast). Historical temp forecast bias is -1.8°F (forecast-minus-observed); refreshed 09:00 forecast is 48°F, calibrated near 49.8°F, now close to live 51°F. Treat this as a stale/biased nowcast, not a sustained regime change. Greenhouse is 68.1°F/0.73 kPa in IDLE; heat1 is on, cooling and wet relays are off, with no equipment-fault signal. Preserve heat-first cold-night protection and live-gated moisture; leave forecast offsets and crop bands unchanged. Prior plan iris-20261109-0200 scored 4 vs anchor 1 (+3): I credited contained temperature and no VPD-high/dew-risk despite only ~4.6h evidence; 105 VPD guardrail events (48 held) and VPD-low stress make that grade overgenerous and efficacy unproven. Result: Plan window was only 0.001 days (~1.4 minutes) before replacement: historical score 68.0, binary temp/VPD 100%/0.9%, nominal stress 0 heat, 0 cold, 0 VPD-high, 0.01h VPD-low, 0 dew-risk. This is too short to test the cloud-deviation response or its expected effects; no causal attribution, crop outcome, resource-cost, or confirmed consumed-target evidence. Treat as insufficient test rather than proof of success. Score: 3/10
Hypothesis
Expected outcome: No equipment fault or overnight wet escalation; preserve temperature safety through frost nights, avoid VPD-low carryover, and retain live-edge assist on clearer dry ramps. Do not claim cloud correction efficacy from forecast or plan persistence.
Setpoints
Monday November 09
Primary crop-band changes:
| Time | Values | Note |
|---|---|---|
| 16:45 | hyst 0.1855 | Early cloud shift; preserve live-edge assist, avoid extra we |
Tactical tunable changes:
| Time | Values | Note |
|---|---|---|
| 16:45 | s2 1.8625; cool_exit 1.78; all_fans 0; dw_stress 0; engage 1.05; all 1.25; pulse 30; gap 52.5; wt 1.4 | Early cloud shift; preserve live-edge assist, avoid extra we |
Tuesday November 10
Primary crop-band changes:
| Time | Values | Note |
|---|---|---|
| 06:00 | hyst 0.1855 | Frost dawn near 36°F; heat-first and low-wet posture, no for |
| 10:00 | hyst 0.1855 | Cloudy dry ramp; allow bounded wet assist only when live VPD |
| 17:00 | hyst 0.1855 | Taper wetting into the 39°F night; retain frost protection a |
Tactical tunable changes:
| Time | Values | Note |
|---|---|---|
| 06:00 | s2 1.8775000000000002; cool_exit 1.78; all_fans 0; dw_stress 0; engage 1.15; all 1.35; pulse 30; gap 56.25; wt 1.3333333333333333 | Frost dawn near 36°F; heat-first and low-wet posture, no for |
| 10:00 | s2 1.8175000000000001; cool_exit 1.78; all_fans 0; dw_stress 0; engage 0.9500000000000001; all 1.15; pulse 30; gap 41.25; wt 1.5666666666666669 | Cloudy dry ramp; allow bounded wet assist only when live VPD |
| 17:00 | s2 1.8775000000000002; cool_exit 1.78; all_fans 0; dw_stress 0; engage 1.1; all 1.3; pulse 30; gap 56.25; wt 1.3533333333333333 | Taper wetting into the 39°F night; retain frost protection a |
Wednesday November 11
Primary crop-band changes:
| Time | Values | Note |
|---|---|---|
| 08:00 | hyst 0.1855 | Post-frost recovery; suppress wet carryover until measured V |
| 10:00 | hyst 0.1855 | Clear dry ramp; restore band-coupled wet assist on live dema |
| 17:00 | hyst 0.1855 | Keep a short live-VPD recovery shoulder, then taper when bel |
Tactical tunable changes:
| Time | Values | Note |
|---|---|---|
| 08:00 | s2 1.8475000000000001; cool_exit 1.78; all_fans 0; dw_stress 0; engage 1.05; all 1.3; pulse 30; gap 48.75; wt 1.4333333333333333 | Post-frost recovery; suppress wet carryover until measured V |
| 10:00 | s2 1.7; cool_exit 1.78; all_fans 0; dw_stress 0; engage 0.9500000000000001; all 1.15; pulse 33.75; gap 33.75; wt 1.6666666666666665 | Clear dry ramp; restore band-coupled wet assist on live dema |
| 17:00 | s2 1.8325; cool_exit 1.78; all_fans 0; dw_stress 0; engage 1; all 1.2; pulse 30; gap 45; wt 1.48 | Keep a short live-VPD recovery shoulder, then taper when bel |
Thursday November 12
Primary crop-band changes:
| Time | Values | Note |
|---|---|---|
| 10:00 | hyst 0.1855 | Dry clear period; use smallest effective wet assist while pr |
Tactical tunable changes:
| Time | Values | Note |
|---|---|---|
| 10:00 | s2 1.7; cool_exit 1.78; all_fans 0; dw_stress 0; engage 0.9500000000000001; all 1.15; pulse 33.75; gap 33.75; wt 1.6666666666666665 | Dry clear period; use smallest effective wet assist while pr |
Changed secondary parameters:
| Time | Parameter | Change |
|---|---|---|
| 16:45 | band_track_fraction | initial 0 |
| 16:45 | cold_vent_guard_delta_f | initial 8 |
| 16:45 | cool_stage2_exit_hysteresis_f | initial 1 |
| 16:45 | direct_wet_stress_min_dew_margin_f | initial 8 |
| 16:45 | direct_wet_stress_vpd_margin_kpa | initial 0.15 |
| 16:45 | dwell_gate_ms | initial 240000 |
| 16:45 | enthalpy_close | initial 1 |
| 16:45 | enthalpy_open | initial -2 |
| 16:45 | fog_escalation_kpa | initial 0.35 |
| 16:45 | heat_hysteresis | initial 1 |
| 16:45 | min_fog_off_s | initial 90 |
| 16:45 | min_fog_on_s | initial 52.5 |
| 16:45 | mist_backoff_s | initial 600 |
| 16:45 | mist_max_closed_vent_s | initial 600 |
| 16:45 | mist_thermal_relief_s | initial 90 |
| 16:45 | mister_all_delay_s | initial 84 |
| 16:45 | mister_engage_delay_s | initial 42 |
| 16:45 | mister_water_budget_gal | initial 120 |
| 16:45 | night_vpd_bias_kpa | initial 0 |
| 16:45 | outdoor_staleness_max_s | initial 600 |
| 16:45 | sw_dwell_gate_enabled | initial 1 |
| 16:45 | sw_fog_closes_vent | initial 1 |
| 16:45 | sw_mister_closes_vent | initial 0 |
| 16:45 | sw_summer_vent_enabled | initial 1 |
| 16:45 | temp_hysteresis | initial 1.78 |
| 16:45 | vent_exchange_fraction | initial 0.3 |
| 16:45 | vent_prefer_dp_delta_f | initial 3 |
| 16:45 | vent_prefer_temp_delta_f | initial 4 |
| 16:45 | vpd_watch_dwell_s | initial 60 |
| 06:00 | direct_wet_stress_min_dew_margin_f | 8 → 10 |
| 06:00 | direct_wet_stress_vpd_margin_kpa | 0.15 → 0.25 |
| 06:00 | fog_escalation_kpa | 0.35 → 0.45 |
| 06:00 | min_fog_off_s | 90 → 96 |
| 06:00 | min_fog_on_s | 52.5 → 50.25 |
| 10:00 | direct_wet_stress_min_dew_margin_f | 10 → 8 |
| 10:00 | direct_wet_stress_vpd_margin_kpa | 0.25 → 0.05 |
| 10:00 | fog_escalation_kpa | 0.45 → 0.25 |
| 10:00 | min_fog_off_s | 96 → 72 |
| 10:00 | min_fog_on_s | 50.25 → 59.25 |
| 17:00 | direct_wet_stress_min_dew_margin_f | 8 → 10 |
| 17:00 | direct_wet_stress_vpd_margin_kpa | 0.05 → 0.2 |
| 17:00 | fog_escalation_kpa | 0.25 → 0.4 |
| 17:00 | min_fog_off_s | 72 → 96 |
| 17:00 | min_fog_on_s | 59.25 → 50.25 |
| 08:00 | direct_wet_stress_vpd_margin_kpa | 0.2 → 0.15 |
| 08:00 | fog_escalation_kpa | 0.4 → 0.35 |
| 08:00 | min_fog_off_s | 96 → 84 |
| 08:00 | min_fog_on_s | 50.25 → 54.75 |
| 10:00 | direct_wet_stress_min_dew_margin_f | 10 → 8 |
| 10:00 | direct_wet_stress_vpd_margin_kpa | 0.15 → 0.05 |
| 10:00 | fog_escalation_kpa | 0.35 → 0.2 |
| 10:00 | min_fog_off_s | 84 → 60 |
| 10:00 | min_fog_on_s | 54.75 → 63.75 |
| 17:00 | direct_wet_stress_vpd_margin_kpa | 0.05 → 0.1 |
| 17:00 | fog_escalation_kpa | 0.2 → 0.3 |
| 17:00 | min_fog_off_s | 60 → 78 |
| 17:00 | min_fog_on_s | 63.75 → 57 |
| 10:00 | direct_wet_stress_vpd_margin_kpa | 0.1 → 0.05 |
| 10:00 | fog_escalation_kpa | 0.3 → 0.2 |
| 10:00 | min_fog_off_s | 78 → 60 |
| 10:00 | min_fog_on_s | 57 → 63.75 |
🌆 Evening Cycle (4:53 PM) — iris-20261109-1652
validated
4/10
band_track_fraction, cold_vent_guard_delta_f, cool_exit_hysteresis_f, cool_stage2_exit_hysteresis_f, cool_stage2_over_high_f, direct_wet_stress_min_dew_margin_f, direct_wet_stress_vpd_margin_kpa, dwell_gate_ms ...
Reflection
Validating previous cycle: iris-20261109-0850
Result: Window-scoped evaluation for iris-20261109-1652 only: 0.309d (~7.4h), planner_score 69.7, contract-2 binary temp/VPD compliance 98.7%/44.5%; nominal stress heat 0.00h, cold 0.03h, VPD-high 0.00h, VPD-low 1.16h; window dew-risk 0.00h. The forecast-conditioned hypothesis was poorly calibrated: outdoor peak 73.9F vs 68F predicted, RH minimum 52% vs 17%, solar peak 578 vs 417 W/m2; cloud actual unavailable. The predicted high cold window mostly fell after this plan ended at 00:18 and was not tested in its own window. VPD-low stayed under the ⇐2h prediction and dew-risk met ⇐0.1h, but the window is partial and neither outcome is causally attributable; guardrail activity and consumed-target, cost, fixed-panel and physical crop evidence are unavailable. Full Nov 9 scorecard context: planner_score 76.6, binary temp/VPD 97.9%/60.4%, stress 0 heat/0.5 cold/0.08 VPD-high/9.42 VPD-low, dew margin minimum 3.6F and dp-risk 0.2h; water 39gal vs 7d average 19gal, cost-electric/gas unavailable and water cost USD 0.19. The full-day VPD-low and dew-risk outcome does not support calling the overnight taper effective; solar-night dryout evidence separately had 17 episodes, 10 ineffective and 7 insufficient-evidence, with safety gate pass but no daytime dry-action or hold-admission samples, so safety is not effectiveness. Score: 4/10
Hypothesis
Testing: Cold-night moisture/dwell balance: restrain wet assist below the live VPD high edge, protect dew margin, and reduce ordinary relay churn. Expected outcome: Overnight cold stress ⇐2h, added VPD-low stress ⇐2h, and dp-risk ⇐0.1h; no forecast-only wetting. Costs remain ungraded because current resource telemetry is unavailable.
Conditions
68.0°F
17.0%
417.0 W/m²
75.0%
House 75.0F/0.72 kPa, dew margin 8.3F; today’s minimum 3.6F. Tonight falls to 36F before dawn with outdoor VPD 0.25-0.31; Tuesday reaches 68F/17% RH and VPD 1.91 with variable cloud. Today score 73 vs 7d 76.5; VPD-low dominates. I graded plans 0640 and 0850 at 3 vs anchors 6: self-grade penalized 2h windows ending before their principal stress periods; anchor favored safe partial windows/no guardrail events. Neither hypothesis was fully tested; no causal credit.
Expected stress windows
Retain heat, avoid unnecessary cold exchange, and damp ordinary mode churn while preserving safety preemption.
Taper wetting below the live high edge; permit only modest edge assist with dew margin at least 10F.
Parameter rationale
Keep wet assist gated near the live high edge and dew-safe; target <=2h added overnight VPD-low stress and <=0.1h dew-risk.
Setpoints
Monday November 09
Primary crop-band changes:
| Time | Values | Note |
|---|---|---|
| 16:45 | hyst 0.17575000000000002 | evening_settle: cool the warm house; avoid wetting below VPD |
Tactical tunable changes:
| Time | Values | Note |
|---|---|---|
| 16:45 | s2 1.8175000000000001; cool_exit 1.6; all_fans 0; dw_stress 1; engage 0.9500000000000001; all 1.15; pulse 33.75; gap 41.25; wt 1.7 | evening_settle: cool the warm house; avoid wetting below VPD |
Tuesday November 10
Primary crop-band changes:
| Time | Values | Note |
|---|---|---|
| 00:00 | hyst 0.21575 | midnight_posture: frost/cold-air protection, low wet duty, h |
| 05:00 | hyst 0.17575000000000002 | pre_dawn: maintain restrained wetting and heat stability; le |
Tactical tunable changes:
| Time | Values | Note |
|---|---|---|
| 00:00 | s2 2.04; cool_exit 2.3200000000000003; all_fans 0; dw_stress 0; engage 1.1; all 1.3; pulse 30; gap 60; wt 1.1666666666666665 | midnight_posture: frost/cold-air protection, low wet duty, h |
| 05:00 | s2 1.8175000000000001; cool_exit 1.6; all_fans 0; dw_stress 1; engage 0.9500000000000001; all 1.15; pulse 33.75; gap 41.25; wt 1.7 | pre_dawn: maintain restrained wetting and heat stability; le |
Changed secondary parameters:
| Time | Parameter | Change |
|---|---|---|
| 16:45 | band_track_fraction | initial 0 |
| 16:45 | cold_vent_guard_delta_f | initial 10 |
| 16:45 | cool_stage2_exit_hysteresis_f | initial 1 |
| 16:45 | direct_wet_stress_min_dew_margin_f | initial 10 |
| 16:45 | direct_wet_stress_vpd_margin_kpa | initial 0.05 |
| 16:45 | dwell_gate_ms | initial 210000 |
| 16:45 | enthalpy_close | initial 1 |
| 16:45 | enthalpy_open | initial -2 |
| 16:45 | fog_escalation_kpa | initial 0.2 |
| 16:45 | heat_hysteresis | initial 1 |
| 16:45 | min_fog_off_s | initial 72 |
| 16:45 | min_fog_on_s | initial 59.25 |
| 16:45 | mist_backoff_s | initial 600 |
| 16:45 | mist_max_closed_vent_s | initial 600 |
| 16:45 | mist_thermal_relief_s | initial 90 |
| 16:45 | mister_all_delay_s | initial 75 |
| 16:45 | mister_engage_delay_s | initial 37.5 |
| 16:45 | mister_water_budget_gal | initial 120 |
| 16:45 | night_vpd_bias_kpa | initial 0 |
| 16:45 | outdoor_staleness_max_s | initial 600 |
| 16:45 | sw_dwell_gate_enabled | initial 1 |
| 16:45 | sw_fog_closes_vent | initial 1 |
| 16:45 | sw_mister_closes_vent | initial 0 |
| 16:45 | sw_summer_vent_enabled | initial 1 |
| 16:45 | temp_hysteresis | initial 1.6 |
| 16:45 | vent_exchange_fraction | initial 0.3 |
| 16:45 | vent_prefer_dp_delta_f | initial 5 |
| 16:45 | vent_prefer_temp_delta_f | initial 6 |
| 16:45 | vpd_watch_dwell_s | initial 52.5 |
| 00:00 | direct_wet_stress_min_dew_margin_f | 10 → 12 |
| 00:00 | direct_wet_stress_vpd_margin_kpa | 0.05 → 0.2 |
| 00:00 | dwell_gate_ms | 210000 → 330000 |
| 00:00 | fog_escalation_kpa | 0.2 → 0.45 |
| 00:00 | min_fog_off_s | 72 → 126 |
| 00:00 | min_fog_on_s | 59.25 → 39 |
| 00:00 | mister_all_delay_s | 75 → 111 |
| 00:00 | mister_engage_delay_s | 37.5 → 55.5 |
| 00:00 | temp_hysteresis | 1.6 → 2.3200000000000003 |
| 00:00 | vpd_watch_dwell_s | 52.5 → 82.5 |
| 05:00 | direct_wet_stress_min_dew_margin_f | 12 → 10 |
| 05:00 | direct_wet_stress_vpd_margin_kpa | 0.2 → 0.05 |
| 05:00 | dwell_gate_ms | 330000 → 210000 |
| 05:00 | fog_escalation_kpa | 0.45 → 0.2 |
| 05:00 | min_fog_off_s | 126 → 72 |
| 05:00 | min_fog_on_s | 39 → 59.25 |
| 05:00 | mister_all_delay_s | 111 → 75 |
| 05:00 | mister_engage_delay_s | 55.5 → 37.5 |
| 05:00 | temp_hysteresis | 2.3200000000000003 → 1.6 |
| 05:00 | vpd_watch_dwell_s | 82.5 → 52.5 |
End-of-Day Summary
Climate
59.1–84.7°F; avg 68.4°F
0.25–1.72 kPa; avg 0.83 kPa
51.9–89.0%
Interior Light Evidence
- Crop DLI: unavailable
- Reason:
source_reading_missing - Provenance:
par_quantum_sensor_canopy - Validity:
dli-validity-v2-par; 2026-11-08T07:57:55.927971+00:00 → open - Qualified-light minutes and photoperiod remain independent of unavailable DLI.
Stress Hours
- Heat stress (>85°F): 0.0h
- VPD stress (>2.0 kPa): 0.1h
- Cold stress (<55°F): 0.5h
Economics
Not available
USD 1.52
USD 0.190
Not available
Equipment Runtimes
| Equipment | Runtime | Reading |
|---|---|---|
| Fan 1 | 24 min | Primary exhaust runtime. |
| Fan 2 | 32 min | Secondary exhaust runtime. |
| Vent | 53 min | Intake vent runtime. |
| Fog | 8 min | Fogger runtime. |
| Heat 1 electric | 1178 min | Electric heater runtime. |
| Heat 2 gas | 146 min | Gas heater runtime. |
| Grow lights | 1091 min | Supplemental lighting runtime. |
| Mister south | 0.00h | South mister runtime. |
| Mister west | 0.00h | West mister runtime. |
| Mister center | 0.02h | Center mister runtime. |
Water
- Total: 39 gal
- Mister: 3 gal
Crop Health (Gemini Vision)
| Crop | Zone | Health | Observations | Note |
|---|---|---|---|---|
| Vanda Orchids | center | 75% | 2 | Observation notes are collapsed below to avoid publishing partial vision snippets. |
Vision observation notes
Hanging baskets visible in the center background. Roots appear white and healthy. Leaves are green and turgid. No obvious signs of wilting or yellowing. || Hanging baskets visible in the center zone. Roots appear exposed and healthy in structure, though low light (0 lux) limits detailed leaf assessment. No obvious wilting or pest damage visible in IR.
Hourly Pattern
| Hour | Temperature | VPD | RH |
|---|---|---|---|
| 10:00 | 73.2°F | 1.00 kPa | 64.4% |
| 11:00 | 74.7°F | 1.03 kPa | 64.9% |
| 12:00 | 76.1°F | 1.12 kPa | 63.7% |
| 13:00 | 76.3°F | 1.19 kPa | 61.6% |
| 14:00 | 80.1°F | 1.14 kPa | 67.8% |
| 15:00 | 81.2°F | 1.05 kPa | 71.6% |
| 16:00 | 75.7°F | 0.81 kPa | 73.2% |
| 17:00 | 71.4°F | 0.76 kPa | 71.3% |
| 18:00 | 69.6°F | 0.69 kPa | 72.0% |
| 19:00 | 69.3°F | 0.88 kPa | 63.8% |
| 20:00 | 66.7°F | 0.81 kPa | 64.1% |
| 21:00 | 64.2°F | 0.71 kPa | 65.6% |
| 22:00 | 63.5°F | 0.71 kPa | 64.4% |
| 23:00 | 61.3°F | 0.59 kPa | 68.3% |
| 00:00 | 60.2°F | 0.53 kPa | 70.2% |
| 01:00 | 60.5°F | 0.60 kPa | 66.9% |
| 02:00 | 59.7°F | 0.58 kPa | 66.7% |
| 03:00 | 61.1°F | 0.74 kPa | 59.9% |
| 04:00 | 61.6°F | 0.79 kPa | 57.8% |
| 05:00 | 62.8°F | 0.83 kPa | 57.4% |
| 06:00 | 63.8°F | 0.76 kPa | 62.3% |
| 07:00 | 66.1°F | 0.48 kPa | 78.3% |
| 08:00 | 67.9°F | 0.71 kPa | 69.8% |
| 09:00 | 70.7°F | 0.87 kPa | 66.1% |
7-Day Stress Context
| Date | Heat | VPD high | Cold |
|---|---|---|---|
| 2026-11-03 | 0.0h | 0.1h | 0.3h |
| 2026-11-04 | 0.0h | 0.4h | 0.8h |
| 2026-11-05 | 0.0h | 0.7h | 1.4h |
| 2026-11-06 | 0.0h | 0.0h | 0.6h |
| 2026-11-07 | 0.0h | 0.0h | 0.7h |
| 2026-11-08 | 0.0h | 0.2h | 0.7h |
| 2026-11-09 | 0.0h | 0.1h | 0.5h |