November 15, 2026
Generated lab notebook from daily_summary, plan_journal, plan_delivery_log, and setpoint audit data. It is intentionally chronological and may include in-progress cycles before validation.
Planner Execution Ledger
Planner checkpoints can acknowledge that the active plan is still suitable without writing a new public plan ID. Those no-change decisions are part of the audit trail.
7
4
2
0
| Event | Delivered | Type | Status | Note |
|---|---|---|---|---|
| End-of-day review and reset | 00:16 | MIDNIGHT | plan_written | Wrote public plan iris-20261115-0016. Resolved 00:18 MDT. |
| Morning planning cycle | 06:47 | SUNRISE | plan_written | Wrote public plan iris-20261115-0647. Resolved 06:51 MDT. |
| Forecast deviation | 10:43 | FORECAST_DEVIATION | plan_written | Wrote public plan iris-20261115-1043. Resolved 10:47 MDT. |
| Solar peak planning checkpoint | 11:45 | SOLAR_MAX | action_completed | Delivery recorded without a public plan write. Resolved 11:47 MDT. |
| Peak Stress | 13:45 | TRANSITION | acked | Acknowledged: No tunable change warranted: fresh climate is 77.6°F, VPD 1.09 kPa, dew margin 12°F, mode IDLE; heat1 alone is on. No current heat or VPD-high stress, and the active staged-wet plan is appropriate as outdoor conditions cool and VPD falls this evening. Resolved 13:46 MDT. |
| Decline | 15:44 | TRANSITION | acked | Acknowledged: No immediate retune: house temp 80.8°F and VPD 1.19 kPa are within the current served bands, dew margin is 11.7°F, and all climate relays are off. The existing 16:30 waypoint already tapers mister thresholds and widens the pulse gap ahead of the cold, humid overnight forecast; localized south/east VPD outliers do not justify overriding that staged posture. Resolved 15:45 MDT. |
| Evening planning cycle | 16:43 | SUNSET | plan_written | Wrote public plan iris-20261115-1643. Resolved 16:47 MDT. |
🌅 Morning Cycle (12:18 AM) — iris-20261115-0016
validated
4/10
band_track_fraction, cold_vent_guard_delta_f, cool_exit_hysteresis_f, cool_stage2_exit_hysteresis_f, cool_stage2_over_high_f, direct_wet_stress_min_dew_margin_f, direct_wet_stress_vpd_margin_kpa, dwell_gate_ms ...
Reflection
Validating previous cycle: iris-20261114-1645
Previous hypothesis: {“conditions”:{“outdoor_temp_peak_f”:45,“outdoor_rh_min_pct”:78,“solar_peak_w_m2”:0,“cloud_cover_avg_pct”:96,“notes”:“Sunset indoor 73.1F/VPD 0.93 kPa vs 0.90 high edge; dew margin 11.7F. Today’s score 76.9, binary temp/VPD 96.0/65.8%, VPD-low stress 5.67h; costs unavailable. The 12h forecast reaches 38F/95% RH/0.04 kPa at 03:00. Main risk is a humid low-VPD trough; preserve stable heat and dew safety, but retain bounded band-edge wet assist if measured VPD remains high. Historical temperature forecasts run about 2.3F cold.”},“stress_windows”:[{“kind”:“vpd_low”,“start”:“2026-11-14T22:00:00-07:00”,“end”:“2026-11-15T05:30:00-07:00”,“severity”:“high”,“mitigation”:“Reduce mist duty and heavy fog as VPD falls; retain bounded band-edge mist only if live VPD remains high and dew margin is safe… Result: Scoped window 0.273 day for iris-20261115-0016: contract-2 planner score 73.6; binary joint/temp/VPD compliance 30.7%/89.8%/34.6%; nominal cold stress 0.29h, VPD-high 0.05h, VPD-low 1.84h, dew-risk 0h. The <2h VPD-low and zero dew-risk goals were met, but joint/VPD compliance remained poor and cold stress was nonzero. Costs, coverage, confirmed consumed targets and physical crop outcomes are unavailable; this supports only a cautious partial score, not causal benefit or a durable lesson. Score: 4/10
Hypothesis
Expected outcome: Through the early-day handoff, maintain zero dew-risk hours and under 1h cold stress if heating capacity permits; avoid forecast-only wetting while keeping assist available near live VPD-high demand. Costs and physical crop outcomes are unavailable.
Setpoints
Sunday November 15
Primary crop-band changes:
| Time | Values | Note |
|---|---|---|
| 00:16 | hyst 0.25625000000000003 | Cold, humid night: restrain wetting but retain band-edge res |
| 03:30 | hyst 0.26125000000000004 | Frost-risk pre-dawn: preserve heat, minimize wet duty and co |
| 06:30 | hyst 0.25125000000000003 | At sunrise, keep dawn moisture conservative until live VPD a |
| 09:30 | hyst 0.24125000000000002 | Early-day handoff: reopen modest band-coupled assist only wi |
Tactical tunable changes:
| Time | Values | Note |
|---|---|---|
| 00:16 | s2 1.995; cool_exit 2.14; all_fans 0; dw_stress 0; engage 0.9500000000000001; all 1.15; pulse 30; gap 60; wt 1.3 | Cold, humid night: restrain wetting but retain band-edge res |
| 03:30 | s2 2.0100000000000002; cool_exit 2.23; all_fans 0; dw_stress 0; engage 0.9500000000000001; all 1.15; pulse 30; gap 60; wt 1.2333333333333334 | Frost-risk pre-dawn: preserve heat, minimize wet duty and co |
| 06:30 | s2 1.98; cool_exit 2.05; all_fans 0; dw_stress 0; engage 0.9500000000000001; all 1.15; pulse 30; gap 60; wt 1.3333333333333333 | At sunrise, keep dawn moisture conservative until live VPD a |
| 09:30 | s2 1.905; cool_exit 1.87; all_fans 0; dw_stress 0; engage 0.9500000000000001; all 1.15; pulse 30; gap 41.25; wt 1.5666666666666669 | Early-day handoff: reopen modest band-coupled assist only wi |
Changed secondary parameters:
| Time | Parameter | Change |
|---|---|---|
| 00:16 | band_track_fraction | initial 0 |
| 00:16 | cold_vent_guard_delta_f | initial 14 |
| 00:16 | cool_stage2_exit_hysteresis_f | initial 1 |
| 00:16 | direct_wet_stress_min_dew_margin_f | initial 8 |
| 00:16 | direct_wet_stress_vpd_margin_kpa | initial 0.05 |
| 00:16 | dwell_gate_ms | initial 300000 |
| 00:16 | enthalpy_close | initial 1 |
| 00:16 | enthalpy_open | initial -2 |
| 00:16 | fog_escalation_kpa | initial 0.4 |
| 00:16 | heat_hysteresis | initial 1 |
| 00:16 | min_fog_off_s | initial 108 |
| 00:16 | min_fog_on_s | initial 45.75 |
| 00:16 | mist_backoff_s | initial 600 |
| 00:16 | mist_max_closed_vent_s | initial 600 |
| 00:16 | mist_thermal_relief_s | initial 90 |
| 00:16 | mister_all_delay_s | initial 102 |
| 00:16 | mister_engage_delay_s | initial 51 |
| 00:16 | mister_water_budget_gal | initial 120 |
| 00:16 | night_vpd_bias_kpa | initial 0 |
| 00:16 | outdoor_staleness_max_s | initial 600 |
| 00:16 | sw_dwell_gate_enabled | initial 1 |
| 00:16 | sw_fog_closes_vent | initial 1 |
| 00:16 | sw_mister_closes_vent | initial 0 |
| 00:16 | sw_summer_vent_enabled | initial 1 |
| 00:16 | temp_hysteresis | initial 2.14 |
| 00:16 | vent_exchange_fraction | initial 0.3 |
| 00:16 | vent_prefer_dp_delta_f | initial 9 |
| 00:16 | vent_prefer_temp_delta_f | initial 10 |
| 00:16 | vpd_watch_dwell_s | initial 75 |
| 03:30 | dwell_gate_ms | 300000 → 315000 |
| 03:30 | fog_escalation_kpa | 0.4 → 0.5 |
| 03:30 | min_fog_off_s | 108 → 114 |
| 03:30 | min_fog_on_s | 45.75 → 43.5 |
| 03:30 | mister_all_delay_s | 102 → 106.5 |
| 03:30 | mister_engage_delay_s | 51 → 53.25 |
| 03:30 | temp_hysteresis | 2.14 → 2.23 |
| 03:30 | vpd_watch_dwell_s | 75 → 78.75 |
| 06:30 | dwell_gate_ms | 315000 → 285000 |
| 06:30 | fog_escalation_kpa | 0.5 → 0.4 |
| 06:30 | min_fog_off_s | 114 → 102 |
| 06:30 | min_fog_on_s | 43.5 → 48 |
| 06:30 | mister_all_delay_s | 106.5 → 97.5 |
| 06:30 | mister_engage_delay_s | 53.25 → 48.75 |
| 06:30 | temp_hysteresis | 2.23 → 2.05 |
| 06:30 | vpd_watch_dwell_s | 78.75 → 71.25 |
| 09:30 | dwell_gate_ms | 285000 → 255000 |
| 09:30 | fog_escalation_kpa | 0.4 → 0.3 |
| 09:30 | min_fog_off_s | 102 → 72 |
| 09:30 | min_fog_on_s | 48 → 59.25 |
| 09:30 | mister_all_delay_s | 97.5 → 88.5 |
| 09:30 | mister_engage_delay_s | 48.75 → 44.25 |
| 09:30 | temp_hysteresis | 2.05 → 1.87 |
| 09:30 | vpd_watch_dwell_s | 71.25 → 63.75 |
🌅 Morning Cycle (6:51 AM) — iris-20261115-0647
validated
4/10
band_track_fraction, cold_vent_guard_delta_f, cool_exit_hysteresis_f, cool_stage2_exit_hysteresis_f, cool_stage2_over_high_f, direct_wet_stress_min_dew_margin_f, direct_wet_stress_vpd_margin_kpa, dwell_gate_ms ...
Reflection
Validating previous cycle: iris-20261114-1645
Result: Scoped only to iris-20261115-0647’s governed 06:51–10:47 MST window (0.164 day): contract-3 binary served-band compliance/planner_score 54.8%, temp 92.5%, VPD 58.3%; stress cold 0.20h, VPD-high 0.03h, VPD-low 1.11h, dew-risk 0h in the scoped scorecard. This directionally matches the forecasted humid-dawn VPD-low risk and conservative wet posture, but the joint/VPD score remained poor; the planned midday live-edge phase was outside this plan’s window. No causal benefit can be claimed: coverage and consumed targets are unverified, resource metrics are unavailable, and no physical crop outcome is qualified. Score: 4/10
Hypothesis
Testing: Test staged wet authority: 10% mist duty through humid morning, then 18% only for live midday edge demand, with conservative fog; measure VPD-low/high, dew risk and guardrail/readback realization. Expected outcome: For 06:46-18:30, target <3h VPD-low stress, zero dew-risk hours and >=90% temp compliance; compare VPD axis and action/guardrail evidence without claiming crop benefit or causality.
Conditions
58.0°F
47.0%
459.0 W/m²
30.0%
Cool high-RH dawn, clouds clear under modest solar, then a cold night. Indoor 63F/VPD 0.84/dew margin 15.2F; South VPD 1.07 versus West 0.71. Yesterday VPD-low stress was 10.75h; costs unavailable. I scored the prior plan 4 vs anchor 1 because its partial-window <2h VPD-low and zero dew-risk goals held, but poor VPD/joint compliance and 70/96 held guardrails weakened attribution.
Expected stress windows
Keep humid-dawn mist duty low and fog conservative; allow only controller-selected, dew-safe drying and verify live VPD.
Retain low-wet, stable evening posture; verify heating and protect the lower edge through the 33F forecast.
Parameter rationale
Stage a modest +0.10-kPa dawn excess with a 10% duty cap, then +0.05 and 18% only at midday, limiting broad wetting while preserving live edge response.
Setpoints
Sunday November 15
Primary crop-band changes:
| Time | Values | Note |
|---|---|---|
| 06:46 | hyst 0.21125000000000002 | Dawn: avoid forecast-only wetting; retain dew-safe, controll |
| 09:30 | hyst 0.21125000000000002 | Morning ramp: hold modest wet duty until live VPD justifies |
| 13:30 | hyst 0.21125000000000002 | Peak: permit band-edge assist for South/local demand, capped |
| 16:30 | hyst 0.21125000000000002 | Decline: taper broad wet authority as solar falls; retain ed |
| 18:30 | hyst 0.22125 | Evening: low-wet and churn-conscious for the cold, low-outdo |
Tactical tunable changes:
| Time | Values | Note |
|---|---|---|
| 06:46 | s2 1.9300000000000002; cool_exit 2.05; all_fans 0; dw_stress 0; engage 1; all 1.1; pulse 30; gap 56.25; wt 1.3666666666666667 | Dawn: avoid forecast-only wetting; retain dew-safe, controll |
| 09:30 | s2 1.8775000000000002; cool_exit 2.05; all_fans 0; dw_stress 0; engage 1; all 1.1; pulse 30; gap 56.25; wt 1.3666666666666667 | Morning ramp: hold modest wet duty until live VPD justifies |
| 13:30 | s2 1.8475000000000001; cool_exit 2.05; all_fans 0; dw_stress 0; engage 0.9500000000000001; all 1.15; pulse 30; gap 48.75; wt 1.4866666666666666 | Peak: permit band-edge assist for South/local demand, capped |
| 16:30 | s2 1.965; cool_exit 2.05; all_fans 0; dw_stress 0; engage 1; all 1.15; pulse 30; gap 56.25; wt 1.3666666666666667 | Decline: taper broad wet authority as solar falls; retain ed |
| 18:30 | s2 1.995; cool_exit 2.23; all_fans 0; dw_stress 0; engage 1; all 1.15; pulse 30; gap 60; wt 1.2866666666666666 | Evening: low-wet and churn-conscious for the cold, low-outdo |
Changed secondary parameters:
| Time | Parameter | Change |
|---|---|---|
| 06:46 | band_track_fraction | initial 0 |
| 06:46 | cold_vent_guard_delta_f | initial 14 |
| 06:46 | cool_stage2_exit_hysteresis_f | initial 1 |
| 06:46 | direct_wet_stress_min_dew_margin_f | initial 9 |
| 06:46 | direct_wet_stress_vpd_margin_kpa | initial 0.1 |
| 06:46 | dwell_gate_ms | initial 285000 |
| 06:46 | enthalpy_close | initial 1 |
| 06:46 | enthalpy_open | initial -2 |
| 06:46 | fog_escalation_kpa | initial 0.4 |
| 06:46 | heat_hysteresis | initial 1 |
| 06:46 | min_fog_off_s | initial 96 |
| 06:46 | min_fog_on_s | initial 50.25 |
| 06:46 | mist_backoff_s | initial 600 |
| 06:46 | mist_max_closed_vent_s | initial 600 |
| 06:46 | mist_thermal_relief_s | initial 90 |
| 06:46 | mister_all_delay_s | initial 97.5 |
| 06:46 | mister_engage_delay_s | initial 48.75 |
| 06:46 | mister_water_budget_gal | initial 120 |
| 06:46 | night_vpd_bias_kpa | initial 0 |
| 06:46 | outdoor_staleness_max_s | initial 600 |
| 06:46 | sw_dwell_gate_enabled | initial 1 |
| 06:46 | sw_fog_closes_vent | initial 1 |
| 06:46 | sw_mister_closes_vent | initial 0 |
| 06:46 | sw_summer_vent_enabled | initial 1 |
| 06:46 | temp_hysteresis | initial 2.05 |
| 06:46 | vent_exchange_fraction | initial 0.3 |
| 06:46 | vent_prefer_dp_delta_f | initial 9 |
| 06:46 | vent_prefer_temp_delta_f | initial 10 |
| 06:46 | vpd_watch_dwell_s | initial 71.25 |
| 13:30 | direct_wet_stress_min_dew_margin_f | 9 → 8 |
| 13:30 | direct_wet_stress_vpd_margin_kpa | 0.1 → 0.05 |
| 13:30 | fog_escalation_kpa | 0.4 → 0.35 |
| 13:30 | min_fog_off_s | 96 → 84 |
| 13:30 | min_fog_on_s | 50.25 → 54.75 |
| 16:30 | direct_wet_stress_min_dew_margin_f | 8 → 9 |
| 16:30 | direct_wet_stress_vpd_margin_kpa | 0.05 → 0.1 |
| 16:30 | fog_escalation_kpa | 0.35 → 0.4 |
| 16:30 | min_fog_off_s | 84 → 96 |
| 16:30 | min_fog_on_s | 54.75 → 50.25 |
| 18:30 | direct_wet_stress_min_dew_margin_f | 9 → 10 |
| 18:30 | dwell_gate_ms | 285000 → 315000 |
| 18:30 | min_fog_off_s | 96 → 108 |
| 18:30 | min_fog_on_s | 50.25 → 45.75 |
| 18:30 | mister_all_delay_s | 97.5 → 106.5 |
| 18:30 | mister_engage_delay_s | 48.75 → 53.25 |
| 18:30 | temp_hysteresis | 2.05 → 2.23 |
| 18:30 | vpd_watch_dwell_s | 71.25 → 78.75 |
☀️ Midday Cycle (10:47 AM) — iris-20261115-1043
validated
4/10
band_track_fraction, cold_vent_guard_delta_f, cool_exit_hysteresis_f, cool_stage2_exit_hysteresis_f, cool_stage2_over_high_f, direct_wet_stress_min_dew_margin_f, direct_wet_stress_vpd_margin_kpa, dwell_gate_ms ...
Reflection
Validating previous cycle: iris-20261115-0016
Previous hypothesis: Nov 14 contract-2 daily planner score was 78.2 (joint 54.1%, temp 95.4%, VPD 55.9%); nominal VPD-low stress 10.33h and cold 1.08h, with resource costs unavailable. Evaluated iris-20261114-1055 at 4/10 vs anchor 5: its 5.83h scoped window scored 77.9, VPD-low 2.61h, cold 0.26h, and no VPD-high/dew-risk; recovery was only partly supported and no durable lesson is justified. Current indoor state is 60.6F, VPD 0.41, dew margin 7.1F with heat1 on. Keep cold-night restraint, avoid chasing the target inside the corridor, and preserve bounded wet assist for a measured rise toward the current VPD high edge. Forecast is stale; an open band-drift alert cites a conflicting older band, so favor fresh climate/action evidence. Result: Scoped 6.0h plan window (2026-11-15 10:47–16:47 MST): contract-3 planner score/joint served-band compliance 54.5%, temp-axis 93.8%, VPD-axis 57.3%; the supplied window row reports no heat stress, ~0.37h cold, ~0.04h VPD-high, and ~2.52h VPD-low. The hypothesis called for carrying the staged wet cap/live-edge gating through the daytime solar deviation and then tapering toward the cold humid night. Temperature stayed strong, but VPD/joint compliance remained weak and low-VPD exposure was not eliminated; no evidence establishes that the wet-cap treatment caused or prevented these outcomes. The forecast solar deviation was real; the scoped window does not establish a repeatable forecast bias. Full-day Nov 15 scorecard (54.1%, temp 93.6%, VPD 56.9%, VPD-low 10.0h, cold 1.5h, dew-risk 0h) is context only, not substituted for the window grade. Coverage/consumed targets and physical crop outcome are unverified; no durable lesson extracted. Score: 4/10
Hypothesis
Testing: Continue the staged wet-authority trial: 10% mist duty through humid morning, then 18% only for live midday edge demand, with conservative fog; measure VPD-low/high, dew risk and guardrail/readback realization. No new treatment claim. Expected outcome: Preserve dew margin >=8°F through the cold night; keep the Sunday 18% wet cap live-edge-only, then taper when measured VPD recovers. Maintain frost-safe posture Monday; enable bounded Tue/Wed dry-ramp response only on live edge evidence, evaluating scoped stress and guardrail holds without claiming crop causality.
Setpoints
Sunday November 15
Primary crop-band changes:
| Time | Values | Note |
|---|---|---|
| 10:30 | hyst 0.1375 | Bright clearing and slight dual-axis edge; preserve live-edg |
| 16:30 | hyst 0.1375 | Taper trial cap at sunset only as VPD recovers; maintain sma |
| 19:00 | hyst 0.1375 | Cold humid night ahead; minimize wetting, preserve heat and |
Tactical tunable changes:
| Time | Values | Note |
|---|---|---|
| 10:30 | s2 1.503; cool_exit 1.6; all_fans 0; dw_stress 1; engage 0.9500000000000001; all 1.15; pulse 33.75; gap 33.75; wt 1.7 | Bright clearing and slight dual-axis edge; preserve live-edg |
| 16:30 | s2 1.6735000000000002; cool_exit 1.6; all_fans 0; dw_stress 1; engage 0.9500000000000001; all 1.15; pulse 33.75; gap 41.25; wt 1.7 | Taper trial cap at sunset only as VPD recovers; maintain sma |
| 19:00 | s2 1.7610000000000001; cool_exit 1.6; all_fans 0; dw_stress 1; engage 0.9500000000000001; all 1.15; pulse 33.75; gap 41.25; wt 1.7 | Cold humid night ahead; minimize wetting, preserve heat and |
Monday November 16
Primary crop-band changes:
| Time | Values | Note |
|---|---|---|
| 05:30 | hyst 0.1375 | Protect through forecast 33°F frost; keep wet assist narrow |
| 11:30 | hyst 0.1375 | Cloudy mild day; keep live-edge authority, avoid additional |
Tactical tunable changes:
| Time | Values | Note |
|---|---|---|
| 05:30 | s2 1.7610000000000001; cool_exit 1.6; all_fans 0; dw_stress 1; engage 0.9500000000000001; all 1.15; pulse 33.75; gap 41.25; wt 1.7 | Protect through forecast 33°F frost; keep wet assist narrow |
| 11:30 | s2 1.6005; cool_exit 1.6; all_fans 1; dw_stress 1; engage 0.9500000000000001; all 1.15; pulse 33.75; gap 41.25; wt 1.7 | Cloudy mild day; keep live-edge authority, avoid additional |
Tuesday November 17
Primary crop-band changes:
| Time | Values | Note |
|---|---|---|
| 10:30 | hyst 0.1375 | Forecast supports dry sunny ramp even after 48h+ VPD correct |
| 16:30 | hyst 0.1375 | Taper after the dry ramp only with observed recovery; retain |
Tactical tunable changes:
| Time | Values | Note |
|---|---|---|
| 10:30 | s2 1.5975000000000001; cool_exit 1.6; all_fans 0; dw_stress 1; engage 0.9500000000000001; all 1.15; pulse 33.75; gap 30; wt 1.7000000000000002 | Forecast supports dry sunny ramp even after 48h+ VPD correct |
| 16:30 | s2 1.8175000000000001; cool_exit 1.6; all_fans 0; dw_stress 1; engage 0.9500000000000001; all 1.15; pulse 33.75; gap 41.25; wt 1.7 | Taper after the dry ramp only with observed recovery; retain |
Wednesday November 18
Primary crop-band changes:
| Time | Values | Note |
|---|---|---|
| 10:00 | hyst 0.1375 | Third-day solar/VPD rise; keep bounded live-edge moisture re |
Tactical tunable changes:
| Time | Values | Note |
|---|---|---|
| 10:00 | s2 1.7875; cool_exit 1.6; all_fans 0; dw_stress 1; engage 0.9500000000000001; all 1.15; pulse 33.75; gap 33.75; wt 1.7 | Third-day solar/VPD rise; keep bounded live-edge moisture re |
Changed secondary parameters:
| Time | Parameter | Change |
|---|---|---|
| 10:30 | band_track_fraction | initial 0 |
| 10:30 | cold_vent_guard_delta_f | initial 14 |
| 10:30 | cool_stage2_exit_hysteresis_f | initial 1 |
| 10:30 | direct_wet_stress_min_dew_margin_f | initial 8 |
| 10:30 | direct_wet_stress_vpd_margin_kpa | initial 0.05 |
| 10:30 | dwell_gate_ms | initial 210000 |
| 10:30 | enthalpy_close | initial 1 |
| 10:30 | enthalpy_open | initial -2 |
| 10:30 | fog_escalation_kpa | initial 0.2 |
| 10:30 | heat_hysteresis | initial 1 |
| 10:30 | min_fog_off_s | initial 60 |
| 10:30 | min_fog_on_s | initial 63.75 |
| 10:30 | mist_backoff_s | initial 600 |
| 10:30 | mist_max_closed_vent_s | initial 600 |
| 10:30 | mist_thermal_relief_s | initial 90 |
| 10:30 | mister_all_delay_s | initial 75 |
| 10:30 | mister_engage_delay_s | initial 37.5 |
| 10:30 | mister_water_budget_gal | initial 120 |
| 10:30 | night_vpd_bias_kpa | initial 0 |
| 10:30 | outdoor_staleness_max_s | initial 600 |
| 10:30 | sw_dwell_gate_enabled | initial 1 |
| 10:30 | sw_fog_closes_vent | initial 1 |
| 10:30 | sw_mister_closes_vent | initial 0 |
| 10:30 | sw_summer_vent_enabled | initial 1 |
| 10:30 | temp_hysteresis | initial 1.6 |
| 10:30 | vent_exchange_fraction | initial 0.3 |
| 10:30 | vent_prefer_dp_delta_f | initial 9 |
| 10:30 | vent_prefer_temp_delta_f | initial 10 |
| 10:30 | vpd_watch_dwell_s | initial 52.5 |
| 16:30 | min_fog_off_s | 60 → 72 |
| 16:30 | min_fog_on_s | 63.75 → 59.25 |
| 19:00 | cold_vent_guard_delta_f | 14 → 15 |
| 19:00 | direct_wet_stress_min_dew_margin_f | 8 → 9 |
| 19:00 | vent_prefer_dp_delta_f | 9 → 10 |
| 19:00 | vent_prefer_temp_delta_f | 10 → 12 |
| 11:30 | cold_vent_guard_delta_f | 15 → 14 |
| 11:30 | direct_wet_stress_min_dew_margin_f | 9 → 8 |
| 11:30 | vent_prefer_dp_delta_f | 10 → 9 |
| 11:30 | vent_prefer_temp_delta_f | 12 → 10 |
| 10:30 | min_fog_off_s | 72 → 54 |
| 10:30 | min_fog_on_s | 59.25 → 66 |
| 16:30 | min_fog_off_s | 54 → 72 |
| 16:30 | min_fog_on_s | 66 → 59.25 |
| 10:00 | min_fog_off_s | 72 → 60 |
| 10:00 | min_fog_on_s | 59.25 → 63.75 |
🌆 Evening Cycle (4:47 PM) — iris-20261115-1643
validated
4/10
band_track_fraction, cold_vent_guard_delta_f, cool_exit_hysteresis_f, cool_stage2_exit_hysteresis_f, cool_stage2_over_high_f, direct_wet_stress_min_dew_margin_f, direct_wet_stress_vpd_margin_kpa, dwell_gate_ms ...
Reflection
Validating previous cycle: iris-20261115-0647
Previous hypothesis: {“conditions”:{“outdoor_temp_peak_f”:58.0,“outdoor_rh_min_pct”:47.0,“solar_peak_w_m2”:459,“cloud_cover_avg_pct”:30.0,“notes”:“Cool high-RH dawn, clouds clear under modest solar, then a cold night. Indoor 63F/VPD 0.84/dew margin 15.2F; South VPD 1.07 versus West 0.71. Yesterday VPD-low stress was 10.75h; costs unavailable. I scored the prior plan 4 vs anchor 1 because its partial-window <2h VPD-low and zero dew-risk goals held, but poor VPD/joint compliance and 70/96 held guardrails weakened attribution.”},“stress_windows”:[{“kind”:“vpd_low”,“start”:“2026-11-15T06:46:00-07:00”,“end”:“2026-11-15T11:00:00-07:00”,“severity”:“medium”,“mitigation”:“Keep humid-dawn mist duty low and fog conservative; allow only controller-selected, dew-safe drying and verify live VPD… Result: Scoped outcome for iris-20261115-1643 only: its governed window was about 7.5 h (16:47–00:16 MST), with contract-3 served-band compliance 63.0%, temp 89.6%, VPD 63.0%; cold stress 0.06 h, VPD-high 0, VPD-low 0.26 h, dew-risk 0.06 h. The predicted VPD-low window was only partly observed; the cold window began after this plan was superseded by iris-20261116-0016. Forecast conditions were materially wrong (outdoor peak 56.1F vs 49F, solar 570 vs 0 W/m2, RH minimum 45% vs 71%). Low stress in the short observed window is not evidence the gap/hysteresis changes caused improvement; coverage, consumed targets, and crop outcomes are unverified. No durable lesson. Score: 4/10
Hypothesis
Testing: Carry forward the staged wet-authority trial: 10% duty cap during humid dawn, only for live-edge demand; no new treatment claim. Expected outcome: By dawn, keep dew margin at or above 8F, cold stress below 1.5h, and avoid additional VPD-low stress from wet assist; retain heat stability and the 10% live-edge cap. Judge only scoped band and guardrail evidence.
Conditions
49.0°F
71.0%
0.0 W/m²
35.667%
Forecast falls to 35F with RH 93-100% and outdoor VPD 0-0.05 before dawn; indoor is 72.9F, VPD 0.80, dew margin 9.8F. Today’s partial VPD-low stress dominates. Prior iris-20261115-0016 self-grade 4 vs anchor 1 over-credited a short window despite weak joint/VPD and many held guardrails; keep attribution cautious.
Expected stress windows
Keep wet assist capped at 10%, live-edge-only; avoid unnecessary mist/fog through the saturated trough.
Protect heat hold with conservative outdoor exchange and anti-churn posture; retain all safety preemption.
Parameter rationale
Limit added humidification during the trough while retaining bounded response to measured VPD-high demand.
Reduce ordinary heat/vent reversals and keep cold stress below 1.5h without delaying safety action.
Setpoints
Sunday November 15
Primary crop-band changes:
| Time | Values | Note |
|---|---|---|
| 16:44 | hyst 0.20550000000000002 | evening_settle: preserve heat; low wet cap and selective exc |
Tactical tunable changes:
| Time | Values | Note |
|---|---|---|
| 16:44 | s2 1.7725000000000002; cool_exit 2.14; all_fans 0; dw_stress 0; engage 1.1; all 1.3; pulse 30; gap 30; wt 1.6 | evening_settle: preserve heat; low wet cap and selective exc |
Monday November 16
Primary crop-band changes:
| Time | Values | Note |
|---|---|---|
| 00:00 | hyst 0.20550000000000002 | midnight_posture: avoid wet overshoot and ordinary heat/vent |
| 05:30 | hyst 0.20550000000000002 | pre_dawn: retain the capped live-edge bridge; let fresh indo |
Tactical tunable changes:
| Time | Values | Note |
|---|---|---|
| 00:00 | s2 1.86; cool_exit 2.14; all_fans 0; dw_stress 0; engage 1.15; all 1.35; pulse 30; gap 30; wt 1.6 | midnight_posture: avoid wet overshoot and ordinary heat/vent |
| 05:30 | s2 1.86; cool_exit 2.14; all_fans 0; dw_stress 0; engage 1.05; all 1.2; pulse 30; gap 30; wt 1.6 | pre_dawn: retain the capped live-edge bridge; let fresh indo |
Changed secondary parameters:
| Time | Parameter | Change |
|---|---|---|
| 16:44 | band_track_fraction | initial 0 |
| 16:44 | cold_vent_guard_delta_f | initial 14 |
| 16:44 | cool_stage2_exit_hysteresis_f | initial 1 |
| 16:44 | direct_wet_stress_min_dew_margin_f | initial 8 |
| 16:44 | direct_wet_stress_vpd_margin_kpa | initial 0.2 |
| 16:44 | dwell_gate_ms | initial 300000 |
| 16:44 | enthalpy_close | initial 1 |
| 16:44 | enthalpy_open | initial -2 |
| 16:44 | fog_escalation_kpa | initial 0.45 |
| 16:44 | heat_hysteresis | initial 1 |
| 16:44 | min_fog_off_s | initial 54 |
| 16:44 | min_fog_on_s | initial 66 |
| 16:44 | mist_backoff_s | initial 600 |
| 16:44 | mist_max_closed_vent_s | initial 600 |
| 16:44 | mist_thermal_relief_s | initial 90 |
| 16:44 | mister_all_delay_s | initial 102 |
| 16:44 | mister_engage_delay_s | initial 51 |
| 16:44 | mister_water_budget_gal | initial 120 |
| 16:44 | night_vpd_bias_kpa | initial 0 |
| 16:44 | outdoor_staleness_max_s | initial 600 |
| 16:44 | sw_dwell_gate_enabled | initial 1 |
| 16:44 | sw_fog_closes_vent | initial 1 |
| 16:44 | sw_mister_closes_vent | initial 0 |
| 16:44 | sw_summer_vent_enabled | initial 1 |
| 16:44 | temp_hysteresis | initial 2.14 |
| 16:44 | vent_exchange_fraction | initial 0.3 |
| 16:44 | vent_prefer_dp_delta_f | initial 9 |
| 16:44 | vent_prefer_temp_delta_f | initial 10 |
| 16:44 | vpd_watch_dwell_s | initial 75 |
| 00:00 | direct_wet_stress_vpd_margin_kpa | 0.2 → 0.25 |
| 05:30 | direct_wet_stress_vpd_margin_kpa | 0.25 → 0.15 |
| 05:30 | fog_escalation_kpa | 0.45 → 0.35 |
End-of-Day Summary
Climate
59.0–82.9°F; avg 68.5°F
0.36–1.45 kPa; avg 0.83 kPa
45.2–79.8%
Interior Light Evidence
- Crop DLI: unavailable
- Reason:
source_reading_missing - Provenance:
par_quantum_sensor_canopy - Validity:
dli-validity-v2-par; 2026-11-08T07:57:55.927971+00:00 → open - Qualified-light minutes and photoperiod remain independent of unavailable DLI.
Stress Hours
- Heat stress (above the served band): 0.0h
- VPD stress (above the served band): 0.2h
- Cold stress (below the served band): 1.5h
Economics
USD 4.45
USD 2.59
USD 0.220
USD 7.26
Equipment Runtimes
| Equipment | Runtime | Reading |
|---|---|---|
| Fan 1 | 63 min | Primary exhaust runtime. |
| Fan 2 | 54 min | Secondary exhaust runtime. |
| Vent | 101 min | Intake vent runtime. |
| Fog | 9 min | Fogger runtime. |
| Heat 1 electric | 1057 min | Electric heater runtime. |
| Heat 2 gas | 250 min | Gas heater runtime. |
| Grow lights | 1186 min | Supplemental lighting runtime. |
| Mister south | 0.00h | South mister runtime. |
| Mister west | 0.00h | West mister runtime. |
| Mister center | 0.00h | Center mister runtime. |
Water
- Total: 47 gal
- Mister: 8 gal
Crop Health (Gemini Vision)
| Crop | Zone | Health | Observations | Note |
|---|---|---|---|---|
| Vanda Orchids | center | 78% | 4 | Observation notes are collapsed below to avoid publishing partial vision snippets. |
Vision observation notes
Plants appear healthy with green foliage and active root growth visible on hanging specimen. No obvious signs of stress. || Plants appear healthy with green foliage and active root systems visible in hanging baskets. No signs of stress or disease. || Plants appear healthy with green foliage; some aerial roots visible. No obvious wilting or discoloration. || Plants appear healthy with visible aerial roots; no obvious signs of stress or disease.
Hourly Pattern
| Hour | Temperature | VPD | RH |
|---|---|---|---|
| 10:00 | 73.0°F | 1.07 kPa | 61.5% |
| 11:00 | 74.6°F | 1.06 kPa | 63.6% |
| 12:00 | 76.1°F | 1.08 kPa | 65.0% |
| 13:00 | 76.5°F | 1.08 kPa | 65.5% |
| 14:00 | 76.7°F | 1.06 kPa | 66.1% |
| 15:00 | 75.6°F | 1.09 kPa | 64.2% |
| 16:00 | 74.3°F | 1.02 kPa | 65.0% |
| 17:00 | 73.3°F | 0.98 kPa | 65.5% |
| 18:00 | 70.8°F | 0.89 kPa | 65.9% |
| 19:00 | 70.0°F | 0.73 kPa | 70.8% |
| 20:00 | 67.6°F | 0.67 kPa | 71.2% |
| 21:00 | 64.2°F | 0.55 kPa | 73.4% |
| 22:00 | 62.8°F | 0.43 kPa | 78.3% |
| 23:00 | 62.3°F | 0.53 kPa | 72.6% |
| 00:00 | 60.4°F | 0.40 kPa | 77.5% |
| 01:00 | 60.7°F | 0.47 kPa | 74.4% |
| 02:00 | 60.4°F | 0.52 kPa | 71.1% |
| 03:00 | 60.8°F | 0.65 kPa | 64.7% |
| 04:00 | 61.5°F | 0.74 kPa | 61.1% |
| 05:00 | 62.2°F | 0.74 kPa | 61.9% |
| 06:00 | 64.0°F | 0.81 kPa | 61.0% |
| 07:00 | 66.7°F | 0.65 kPa | 71.5% |
| 08:00 | 68.9°F | 0.84 kPa | 66.0% |
| 09:00 | 69.7°F | 1.04 kPa | 58.5% |
7-Day Stress Context
| Date | Heat | VPD high | Cold |
|---|---|---|---|
| 2026-11-09 | 0.0h | 0.1h | 0.5h |
| 2026-11-10 | 0.0h | 0.1h | 0.8h |
| 2026-11-11 | 0.0h | 0.0h | 0.3h |
| 2026-11-12 | 0.0h | 0.1h | 0.4h |
| 2026-11-13 | 0.0h | 0.0h | 0.4h |
| 2026-11-14 | 0.0h | 0.0h | 1.1h |
| 2026-11-15 | 0.0h | 0.2h | 1.5h |